Installation / Operation Instruction Manual
BLP SERIES Install, Operation, and Maintenance Manual
SECTION 3: OPERATION AND CONTROLS
Rev-1 Bradford White • 200 Lafayette St. • Middleville, MI 49333 Page 36 of 83
BrutePlate Manual Phone: (800) 531-2111 • Website: www.BradfordWhite.com 02/26/2020
3.11.5 Modbus/BACnet Data Addresses and Points
Item Description
Type
Modbus
Address
BACnet
Address
Register
Comments
Remote/Local Setpoint
float32
2
Analog Value
#38
RW
40-180°F Range
(140°F Default)
Unit Remote On/Off
float32
277
Analog Value
#53
RW
0: Off
1: On
Outlet Water
Temperature
float32
289
Analog Input #1
RO
40-205°F
Range
Mixed Inlet Water
Temperature
float32
290
Analog Input #2
RO
40-205°F
Range
Control Valve Open
%age
float32
4
Analog Input #10
RO
0–100%
Range
High Temperature
Alarm Status
bool
2149
Binary Input #10
RO
0: Off
1: On
(Default 20°F
above Setpoint)
Low Temperature
Alarm Status
bool
2245
Binary Input #14
RO
0: Off
1: On
(Default 20°F
below Setpoint)
Outlet Sensor Status
Unit8
1932
MSI#1
RO
0: Good
1: Fail
Inlet Sensor Status
Unit8
1948
MSI#2
RO
0: Good
1: Fail
Notes:
1. Modbus decimal address is offset from 400001
2. Abbreviations
a. RO – Read Only
b. RW – Read/Write