SECTION 3: OPERATION AND CONTROLS
Rev-1 Bradford White 200 Lafayette St. Middleville, MI 49333 Page 44 of 83
BrutePlate Manual Phone: (800) 531-2111 Website: www.BradfordWhite.com 02/26/2020
3.12 DRY CONTACTS
The following two types of contacts are available for remote monitoring of unit:
3.12.1 Contact closure input (enable/disable)
Dry Contacts C and LA are available on the PID temperature controller to remotely start/stop the
unit if required.
This input is supplied with the current transformer. Contact closure on the remote switch disable
(stop) the unit.
3.12.2 Fault Relay Contacts
Fault relay R1 terminals 11 and 14 shown below (also shown in Section 6.4) available on the
terminal block inside the control panel box for remote alarm indication purposes. This relay is a
Double Pole Double Throw (DPDT) type which energizes when fault condition occurs. Fault can
be cleared by pressing the Alarm Silence button.
It has one set of normally open contacts (between contacts 11 and 14 and 21 and 24) and
normally closed contacts (between contacts 11 and 12 and 21 and 22). Normally open (NO)
contacts are rated for 8 amps and maximum switching voltage is 400 VAC.