SECTION 3: OPERATION AND CONTROLS
Rev-1 Bradford White • 200 Lafayette St. • Middleville, MI 49333 Page 40 of 83
BrutePlate Manual Phone: (800) 531-2111 • Website: www.BradfordWhite.com 02/26/2020
10. In order to change the appropriate communication settings:
a. Modbus RTU settings - refer to steps 11 and 12 below. Then jump to step 23.
b. Modbus/BACnet IP settings - refer to steps 13 through 25. Ignore steps 11 and 12
below.
11. Click on scroll button and you will see F.COm:
From the sub-menu, you are able to set up the parameters for Modbus RTU.
12. Now click on scroll button and then click on raise button to select
. Then click on scroll and you will see the following parameters for
Modbus RTU:
a. Default Baud rate: 19200
b. Click on scroll button
c. Default Parity: None
d. Click on scroll button
e. Slave node. Default: 1
Use the raise and/or lower arrow buttons to change the parameters.
Jump to step 23 in order to save the settings.