Boiler Type of Valve
Model Size Sufx* Gas Part No. Mfr. No. Manufacturer
BJVS 50-75 D NAT V0077400 VR8304H HONEYWELL
BJVS 100-225 K NAT V0079000 VR8304H HONEYWELL
BJVS 50-75 D LP V0077500 VR8304H HONEYWELL
BJVS 100-225 K LP V0079100 VR8304H HONEYWELL
BJVH 50-160 C NAT V2001800 SV9501H HONEYWELL
BJVH 225 C NAT V2001900 SV9601H HONEYWELL
BJVH 50-225 C LP V2002300 SV9501H HONEYWELL
*Sufx Denitions C = On/Off Firing
D = On/Off Firing
K = Two-Stage Firing
Table 1 - Gas Control Valves
H2360400B
D. Air Shutter Adjustment (when required)
1. STOP! Read the safety information on the last page.
2. Perform a System Start-Up in accordance with
Section A of this manual.
3. Remove the burner cover by loosening the two
thumbscrews.
4. Observe the ame pattern on all burners. If the
ame on any burner is pulsing, unstable or lifting
continue with this procedure. Otherwise skip to
step 10.
5. On all burners exhibiting an abnormal ame, loosen
but do not remove the air shutter locking screw
using a 5/16 inch wrench. (See Fig. 5 below.)
6. On each affected burner, slowly close the air
shutter until a normal ame is observed, then re-
tighten its associated locking screw.
7. Turn the boiler off.
8. Perform a System Start-Up in accordance with
Section A of this manual.
9. Observe the ame pattern on all burners. If
the ame on any burner is pulsing, unstable or
lifting, repeat steps 5 and 6 until all burners are
exhibiting a normal ame.
10. Re-install the burner cover and tighten it in place.
LOCKING SCREW
(5/16" HEAD)
AIR SHUTTER
BURNER
Figure 5 - Removing the Air Shutter Locking Screw