1C. Heater Identication
Consult the rating plate on the boiler. The following
example simplies the heater identication:
SECTION 2.
Boiler Assembly and Placement
2A. Field Assembly
These boilers are available in two congurations; the
JVH has a hot surface ignition pilot and integral draft
fan, and the JVS has an electronic intermittent ignition
device (I.I.D.). Look for the model designation on the
rating plate, which can be found on top of the boiler in
the right rear corner.
The Bradford White automatic vent dampers are
standard on all JVS models. The Bradford White
side wall power venters can be used on JVS models.
Special instructions for their installation are included
in the vent damper and power venter package. Read
them carefully before installation.
JVS
1st thru 3rd CharaCters (Model designation)
BJV = Bradford White Corp. Model JV
Brute Mini
4th CharaCter (ignition systeM)
s = spark ignition
h = hot surfaCe pilot
5th thru 7th CharaCters (size)
input MBtu / h
8th CharaCter (fuel)
n = natural gas
p = propane gas
9th CharaCter (firing systeM)
D = on / off
10th CharaCter (ConstruCtion option)
i = (standard)
J = puMp (050-125 only)
11th CharaCter (altitude in feet)
s = (0 - 2,000) natural or (0 - 5,000) propane
h = (2,001 - 5,000) natural
i = (5,001 - 8,000) natural and propane
J = (8,001 - 10,000 natural and propane
12th CharaCter (Country)
u = usa & Canada
13th CharaCter (reVision)
2 = seCond reVision
JVH
1st thru 3rd CharaCters (Model designation)
BJV = Bradford White Corp. Model JV
Brute Mini
4th CharaCter (ignition systeM)
s = spark ignition
h = hot surfaCe pilot
5th thru 7th CharaCters (size)
input MBtu / h
8th CharaCter (fuel)
n = natural gas
p = propane gas
9th CharaCter (firing systeM)
C = on / off
10th CharaCter (ConstruCtion option)
s = standard
11th CharaCter (altitude in feet)
s = (0 - 2,000) natural or (0 - 5,000) propane
h = (2,001 - 5,000) natural
i = (5,001 - 8,000) natural and propane
J = (8,001 - 10,000 natural and propane
12th CharaCter (Country)
u = usa & Canada
13th CharaCter (reVision)
2 = seCond reVision
MODEL
J V
IGNIT
SYST
S
H
SIZE
0 5 0
0 7 5
1 0 0
1 2 5
1 6 0
2 2 5
FUEL
N
P
FIRING
SYST
C
D
CONST
OPTION
S
P
I
J
ALTITUDE
S
H
I
J
REVISION
2
BRADFORD
WHITE
COUNTRY
U
VJ U 2B
Table 1. Boiler Model Identication.
1 2 4 5 6 7 8 9 10 11 12 13
3