Installation / Operation Instruction Manual

Table Of Contents
Page 89
Figure 40. External Firing Rate Example
8.D.8.b External Firing Rate
With External Firing Rate selected, the unit will initiate a heat demand once the analog input signal exceeds the
Demand On value. Once the demand is initiated, the analog input signal must be lower than Demand O󰀨 to
remove the heat demand. The external analog signal will activate stages as shown in Figure 40. In this control
mode, if the unit outlet temperature exceeds the Auto Reset High Limit setting, the boiler will shut down and an
“Auto Reset High Limit” condition will appear on the Messages screen. Once the outlet temperature decreases
below the value of (Auto Reset High Limit – Reset Di󰀨erential), the boiler will turn back on at the ring rate set by
the analog input signal.
CONFIGURATION
8.D.9 Time & Date
To navigate to the Time & Date Quick Start Screen, touch the Time and Date area of ANY Screen.
NOTE: The Time is set in a 24 hour parameter but displays only as a 12 hour clock with the
AM / PM automatically added.
The Time & Date Quick Start Screen allows adjustment of the following parameters:
Hour
Minute
Month
Day
Year