Installation / Operation Instruction Manual
Table Of Contents
- Cover
- TABLE OF CONTENTS
- General Information
- SECTION 2 Venting and Combustion Air
- SECTION 3 Gas supply and Piping
- SECTION 4 Water Flow and Headloss Data
- SECTION 5 Boiler Piping
- SECTION 6 Condensate Drain Trap
- SECTION 7 Electrical Connections
- 7.A Installation Warnings
- 7.B Main Power Connections
- 7.C Main Power Data
- 7.D Control Panel Layout
- 7.E Field Connections
- 7.E.1 Power
- 7.E.2 Dry Contacts
- 7.E.3 Temperature Sensors
- 7.E.4 Safety Chain
- 7.E.5 Isolation Valve
- 7.E.6 Heat Demands
- 7.E.7 Analog In and Analog Out
- 7.E.8 Dry Contacts. Run & Alarm
- 7.E.9 RS 485 for Cascade (Lead Lag)
- 7.E.10 RS485 BMS
- 7.F Modbus to BACnet Memory Map (4 pages)
- 7.G WiringDiagram
- 7.H High Voltage Wiring Diagrams (5 pages)
- 7.I Ladder Diagrams (8 pages)
- SECTION 8 Control Operation
- 8.A The Home Screen
- 8.B Login to Lock / Unlock the Display Screen
- 8.C Quick Start
- 8.D Configuration
- 8.E Service Screens
- 8.E.1 Burner
- 8.E.2 Digital I/O ( Input / Output )
- 8.E.3 Analog I/O
- 8.E.4 Screen Settings Timeout
- 8.E.5 History
- 8.E.6 Restart Touchscreen & Recalibrate
- 8.E.7 Factory Reset
- 8.E.8 HMI Model OEM only
- 8.E.9 BIC Model OEM only
- 8.E.10 Both Model. OEM only.
- 8.E.11 About (the Firmware)
- 8.E.12 O2 (Trim Set Point)
- 8.E.13 LMV
- 8.F Messages and USB
- 8.G Active Demands
- SECTION 9 Parameter Tables (3 pages)
- SECTION 10 Initial startupInstructions
- SECTION 11 Maintenance
- SECTION 12 Troubleshooting
- SECTION 13 Replacement Parts
- 13.A Frame and Jacket Assembly, Part Numbers
- 13.B Control Panel Assembly, Part Numbers
- 13.C Blower and Burner Assembly,Part Numbers. ALL Sizes
- 13.D AC Distribution Box Assemblies and Part Numbers
- 13.E Burner Door Part Numbers
- 13.F Waterway Inlet Assembly, Part Numbers
- 13.G Waterway Outlet Assembly, Part Numbers
- 13.H Gas Train Part Numbers
- 13.I Exhaust Manifold Part Numbers
Page 73
Figure 34. Outdoor Reset Example
When there is an active outdoor
reset condition, the set point
will be a calculated value
(CSP) based on the outdoor
reset settings. The example in
gures 41 and 42, shows that
the Outdoor Air Temperature is
42°F. Based on this, and without
a call for DHW, the set point
(CSP) is 160°F. As the outdoor air
temperature increases, the CSP
decreases.
8.D.3 Outdoor Reset
Outdoor reset adjusts a boiler’s setpoint based on outdoor air temperature. This is for boilers only, and is not
used for domestic water. The Outdoor Parameters Screen allows the adjustment of the following parameters:
• Enable/Disable – Enables and disables the outdoor reset functionality.
• Maximum Outdoor Temperature – The outdoor temperature at which the unit will start using the minimum
water temperature as the set point.
• Minimum Outdoor Temperature – The outdoor temperature at which the unit will start using the maximum
water temperature as the set point.
• Maximum Water Temperature – The maximum boiler outlet temperature based on the Minimum Outdoor
Temperature.
• Minimum Water Temperature – The minimum boiler outlet temperature based on the Maximum Outdoor
Temperature.
CONFIGURATION
Figure 33. Status Window,
Outdoor Reset Example
CH1 and CH2 use the set points on the Parameter
screen as the “Max Hot Water Temp” allowing two
distinct curves based on the demand in use.