Installation / Operation Instruction Manual

Table Of Contents
Page 40
GND
GND
GND
GND
GND
GND
120 N
120 N
120 N
120 N
120 L
120 L
120 L
120 L
24 N
24 N
24 N
24 N
24 L
24 L
24 L
24 L
BOILER PUMP N
BOILER PUMP L
AUXILIARY N
AUXILIARY L
DHW PUMP
DHW PUMP
SYSTEM PUMP
SYSTEM PUMP
ISOLATION VALVE
ISOLATION VALVE
ALARM BELL
ALARM BELL
SYSTEM SUPPLY
SYSTEM SUPPLY
SYSTEM RETURN
SYSTEM RETURN
DHW
DHW
OUTDOOR
OUTDOOR
FIELD INTERLOCK
FIELD INTERLOCK
PROOF OF
CLOSE
PROOF OF
OPEN
TT-1
TT-1
TT-2
TT-2
DHW
DHW
BMS 0-10VDC -
BMS 0-10VDC +
PUMP 0-10VDC -
PUMP 0-10VDC +
RUN - C
RUN - N.C.
RUN - N.O.
ALARM - C
ALARM - N.C.
ALARM - N.O.
CASCADE B
CASCADE A
CASCADE GND
BMS B
BMS A
BMS GND
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
RUN RELAY
CONTACTS
ALARM RELAY
CONTACTS
CASCADE
RS485
BMS RS485
ANALOG
OUTPUT
ANALOG
INPUT
SAFETY
CHAIN
ISOLATION
VALVE
HEAT DEMANDSTEMPERATURE SENSOR INPUTSDRY CONTACTS
POWER
OUTPUTS
120 VAC
H2406100A
24 VAC
Figure 20. Field Connections Terminal Block
Figure 19. Control Panel Components
GND
GND
GND
GND
GND
GND
120 N
120 N
120 N
120 N
120 L
120 L
120 L
120 L
24 N
24 N
24 N
24 N
24 L
24 L
24 L
24 L
BOILER PUMP N
BOILER PUMP L
AUXILIARY N
AUXILIARY L
DHW PUMP
DHW PUMP
SYSTEM PUMP
SYSTEM PUMP
ISOLATION VALVE
ISOLATION VALVE
ALARM BELL
ALARM BELL
SYSTEM SUPPLY
SYSTEM SUPPLY
SYSTEM RETURN
SYSTEM RETURN
DHW
DHW
OUTDOOR
OUTDOOR
FIELD INTERLOCK
FIELD INTERLOCK
PROOF OF
CLOSE
PROOF OF
OPEN
TT-1
TT-1
TT-2
TT-2
DHW
DHW
BMS 0-10VDC -
BMS 0-10VDC +
PUMP 0-10VDC -
PUMP 0-10VDC +
RUN - C
RUN - N.C.
RUN - N.O.
ALARM - C
ALARM - N.C.
ALARM - N.O.
CASCADE B
CASCADE A
CASCADE GND
BMS B
BMS A
BMS GND
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
RUN RELAY
CONTACTS
ALARM RELAY
CONTACTS
CASCADE
RS485
BMS RS485
ANALOG
OUTPUT
ANALOG
INPUT
SAFETY
CHAIN
ISOLATION
VALVE
HEAT DEMANDS
TEMPERATURE SENSOR INPUTSDRY CONTACTS
POWER
OUTPUTS
120 VAC
H2406100A
24 VAC
LMV Controller Assembly
Low Water Cut-O󰀨
Handset, Display and
Operating Unit.
For Certied and
Trained Field
Techs Only.
12 Volt DC Power
Supply
Linc Controller
Assembly
O2 Sensor
Controller
Field Connections
Terminal Block
7.D Control Panel Layout
7.E Field Connections
Wiring for all eld connections must be run through the
available electrical conduit to the low voltage box at the
back of the unit. See Figure 18.
Refer to Figure 20 in reference to Sections 7.E.1 thru
7.E.10
7.E.1 Power
Boiler Pump – If connecting a boiler contactor or pump,
use terminals 23 (neutral) and 24 (line voltage). The
output of these terminals is 120VAC with a maximum
output current of 1.5 amps. Boiler pump functionality is
congured using the touch screen.
Auxiliary – no functionality is available on this unit.
7.E.2 Dry Contacts
DHW Pump - If connecting a domestic hot water (DHW)
pump, use terminals 27 and 28 (See Figure 20). This is
a dry contact. The DHW pump supply voltage or DHW
pump relay coil voltage should be applied at terminal
27, and when the DHW pump is called, would be switch
to terminal 28. Contact ratings are 250VAC, 1.5A