Figure 13. Multiple Boilers, P/S Piping for Space Heating and simultaneous
DHW heating w/ parallel piped single boiler
Control:
Use outdoor reset to maintain building loop
temperature.See Section 8.C.3 on page 67.
Set System pump to AUTO, pump runs during space
heating when outdoor temperature is below warm
weather shutdown.
Place jumper on T-T on the Lead Boiler for constant
heating call; or interrupted if so desired.
System sensor required for cascade, outdoor reset
operation and connected to Lead boiler; place sensor in
common header 6 pipe diameters from last connected
unit. See Section 8.D.3 on page 73.
Boiler, System and DHW pumps controlled by The
Touchscreen Control.
Pump operation congurable in pump conguration menu.
See Section 8.D.5 on page 83.
Use on Lag Boiler DHW sensor, terminals 39 and 40, or
aquastat, terminals 53 and 54.
Lag Boiler Pump must be OFF during DHW operation.
Lag Boiler must be congured for local DHW demand
priority; DHW Pump must be wired to Lag Boiler.
BMS control:
For Modbus/BACnet BMS mapping, refer to Section 7.F
on page 44
Enable/disable boiler via T-T terminals (49, 50) for space
heating.
To enable/disable boiler for DHW using an aquastat, use
terminals 53 and 54.
To enable/disable boiler for DHW using a sensor, use
terminals 39 and 40.
BMS can control ring rate or setpoint via terminals 55
and 56. (analog input).
System pump controlled by BMS or The Touchscreen
Control.
NOTE: This drawing is a schematic
representation of a piping style and is
not intended to be used as a working
installation drawing. Local code
requirements must be met.