5.D Suggested Boiler Piping Schematics (continued)
NOTE: Domestic circulator MUST be sized for
both the indirect and the boiler.
Figure 11. Single Boiler, Variable Primary Space Heating with Parallel Piping for indirect Tank
Control:
Use outdoor reset to maintain building loop temperature. See
Section 8.C.3 on page 67.
Set System pump to AUTO, pump runs during space heating
when outdoor temperature is below warm weather shutdown.
Place jumper on T-T for constant heating call; or interrupted if
so desired.
System and DHW pumps all controlled by The Touchscreen
Control. Boiler pump not used.
Pump operation congurable in pump conguration menu.
See Section 8.D.5 on page 83
Use DHW sensor, terminals 39 and 40, or aquastat,
terminals 53 and 54.
System Pump must be OFF during DHW operation for
DHW priority.
BMS control:
For Modbus/BACnet BMS mapping, refer to Section 7.F on
page 44
Enable/disable boiler via T-T terminals (49, 50) for space
heating.
To enable/disable boiler for DHW using an aquastat, use
terminals 53 and 54.
To enable/disable boiler for DHW using a sensor, use
terminals 39 and 40.
BMS can control ring rate or setpoint via terminals 55 and
56. (analog input).
System, boiler and DHW pumps controlled by BMS or The
Touchscreen Control.
NOTE: This drawing is a schematic
representation of a piping style and is
not intended to be used as a working
installation drawing. Local code
requirements must be met.