CONFIGURATION
8.D.4.c Redundancy
To navigate to the Cascade Redundancy Screen, touch the Cascade Icon on the Conguration Screen, then touch the
Redundancy Icon on the Cascade Conguration Screen.
The Cascade Redundancy Screen allows the selection of one of three options for redundancy in cascade systems.
These options are:
Boiler Internal Set Point – In a cascade conguration, upon loss of communication with the lead unit, the lag units
will continue to operate in the same manner as when the communication stopped. For example, if a lag unit was
ring to satisfy a cascade heat demand, it will continue to satisfy the heat demand upon loss of communication with
the Leader.
Redundant Lead – In a cascade conguration, upon loss of communication with the lead unit, a second unit will
assume lead responsibilities.
Disable Redundancy – In a cascade conguration, upon loss of communication with the lead unit, lag units will no
longer satisfy the cascade heat demand.