NOTE: Domestic circulator MUST be sized for
both the indirect and the boiler.
Figure 10. Single Boiler, P/S Piping for Space Heating with Parallel Piping for indirect Tank
Control:
Use outdoor reset to maintain building loop temperature. See Section
8.C.3 on page 67.
Set System pump to AUTO, pump runs during space heating when
outdoor temperature is below warm weather shutdown.
Place jumper on T-T for constant heating call; or interrupted if so
desired.
System sensor required for outdoor reset operation in this application.
Boiler, System and DHW pumps controlled by The Touchscreen
Control.
Pump operation congurable in pump conguration menu. See Section
8.D.5 on page 83
Use DHW sensor, terminals 39 and 40, or aquastat, terminals 53 and
54.
Boiler pump must be OFF during DHW operation for DHW priority.
BMS control:
For Modbus/BACnet BMS mapping, refer to Section 7.F on page 44
Enable/disable boiler via T-T terminals (49, 50) for space heating.
To enable/disable boiler for DHW using an aquastat, use terminals 53
and 54.
To enable/disable boiler for DHW using a sensor, use terminals 39 and
40.
BMS can control ring rate or setpoint via terminals 55 and 56. (analog
input).
System, boiler and DHW pumps controlled by BMS or The
Touchscreen Control.
NOTE: This drawing is a schematic
representation of a piping style and is
not intended to be used as a working
installation drawing. Local code
requirements must be met.