Installation / Operation Instruction Manual

Table Of Contents
Page 27
Air Vent
On innitial installations, drain and ush the system before
adding propylene glycol. Sludge and other sediments in the
boiler can inhibit ow, resulting in rapid breakdown of glycol.
Check the propylene glycol concentration annually. Add
more water or propylene glycol as needed.
The boiler control o󰀨ers some assistance with freeze
protection, as long as the boiler is energized and able to re.
1. If the outlet sensor detects less than 45°F, the
control energizes the boiler pump.
2. If the outlet sensor detects less than 35°F, the
control will re at low rate.
3. Once in freeze protect mode, the boiler will remain in
that state until the outlet sensor detects greater than
50°F.
5.D Suggested Boiler Piping Schematics
This boiler is a high e󰀩ciency appliance. Boiler
e󰀩ciency can be maximized by using piping and
distribution congurations that return the lowest
temperature possible to the boiler, while still meeting the
needs of the system.
Figure 8 on page 27 through Figure 15 on page 34
show suggested piping congurations for boilers. These
diagrams are only meant as guides. All components or
piping required by local code must be installed.
For multi-boiler installations where a primary only
conguration is used, an optional water isolation valve
is available. This valve is eld installed but comes with a
wiring harness which connects with pre-installed boiler
wiring via a quick disconnect connector. The control
system contains the necessary logic to open and close
the insolation valves in conjunction with the boiler heat
demand while always maintaining an open valve to
maintain system ow.
NOTE: This drawing is a schematic
representation of a piping style and is not
intended to be used as a working installation
drawing. Local code requirements must be met.
Control:
Use outdoor reset to maintain building loop temperature. See Section
8.C.3 on page 67.
Set System pump to AUTO, pump runs during space heating when
outdoor temperature is below warm weather shutdown.
Place jumper on T-T for constant heating call; or interrupted if so
desired.
BMS control:
For Modbus/BACnet BMS mapping, refer to Section 7.F on page 44.
Enable/disable boiler via T-T terminals (49, 50).
BMS can control ring rate or setpoint via terminals 55 and 56. (analog
input).
System pump control by BMS or Touchscreen Control.
Figure 8. Single Boiler, Variable Primary, Space Heating only