Installation / Operation Instruction Manual
Table Of Contents
- Cover
- TABLE OF CONTENTS
- General Information
- SECTION 2 Venting and Combustion Air
- SECTION 3 Gas supply and Piping
- SECTION 4 Water Flow and Headloss Data
- SECTION 5 Boiler Piping
- SECTION 6 Condensate Drain Trap
- SECTION 7 Electrical Connections
- 7.A Installation Warnings
- 7.B Main Power Connections
- 7.C Main Power Data
- 7.D Control Panel Layout
- 7.E Field Connections
- 7.E.1 Power
- 7.E.2 Dry Contacts
- 7.E.3 Temperature Sensors
- 7.E.4 Safety Chain
- 7.E.5 Isolation Valve
- 7.E.6 Heat Demands
- 7.E.7 Analog In and Analog Out
- 7.E.8 Dry Contacts. Run & Alarm
- 7.E.9 RS 485 for Cascade (Lead Lag)
- 7.E.10 RS485 BMS
- 7.F Modbus to BACnet Memory Map (4 pages)
- 7.G WiringDiagram
- 7.H High Voltage Wiring Diagrams (5 pages)
- 7.I Ladder Diagrams (8 pages)
- SECTION 8 Control Operation
- 8.A The Home Screen
- 8.B Login to Lock / Unlock the Display Screen
- 8.C Quick Start
- 8.D Configuration
- 8.E Service Screens
- 8.E.1 Burner
- 8.E.2 Digital I/O ( Input / Output )
- 8.E.3 Analog I/O
- 8.E.4 Screen Settings Timeout
- 8.E.5 History
- 8.E.6 Restart Touchscreen & Recalibrate
- 8.E.7 Factory Reset
- 8.E.8 HMI Model OEM only
- 8.E.9 BIC Model OEM only
- 8.E.10 Both Model. OEM only.
- 8.E.11 About (the Firmware)
- 8.E.12 O2 (Trim Set Point)
- 8.E.13 LMV
- 8.F Messages and USB
- 8.G Active Demands
- SECTION 9 Parameter Tables (3 pages)
- SECTION 10 Initial startupInstructions
- SECTION 11 Maintenance
- SECTION 12 Troubleshooting
- SECTION 13 Replacement Parts
- 13.A Frame and Jacket Assembly, Part Numbers
- 13.B Control Panel Assembly, Part Numbers
- 13.C Blower and Burner Assembly,Part Numbers. ALL Sizes
- 13.D AC Distribution Box Assemblies and Part Numbers
- 13.E Burner Door Part Numbers
- 13.F Waterway Inlet Assembly, Part Numbers
- 13.G Waterway Outlet Assembly, Part Numbers
- 13.H Gas Train Part Numbers
- 13.I Exhaust Manifold Part Numbers
Page 33
Figure 14. Multiple Boilers, P/S Piping for Space Heating with redundant P/S for Indirect Tank
Control:
• Use outdoor reset to maintain building loop temperature.
See Section 8.C.3 on page 67.
• Set System pump to AUTO, pump runs during space
heating when outdoor temperature is below
warm weather shutdown.
• Place jumper on T-T on Lead Boiler for constant heating call; or
interrupted if so desired.
• System sensor required for cascade, outdoor reset operation
and connect to Lead boiler; place system sensor as shown,
depending on low or high temperature space heating
application.
• Boiler, System and DHW pumps controlled by The Touchscreen
Control.
• Pump operation congurable in pump conguration menu. See
Section 8.D.5 on page 83
• Use DHW sensor, terminals 39 and 40, or aquastat, terminals
53 and 54 and connect to Lead Boiler.
• During DHW operation, System pump must be OFF in low
temperature space heating applications. In high temperature
applications, System pump can continue to operate.
• Caution: Boiler ring rates during DHW heating may need to
be lowered to prevent burner short cycling. Consult factory for
set-up guidance.
BMS control:
• Enable/disable boiler via T-T terminals (49, 50) for space
heating.
• To enable/disable boiler for DHW using an aquastat, use
terminals 53 and 54.
• To enable/disable boiler for DHW using a sensor, use terminals
39 and 40.
• BMS can control ring rate or setpoint via terminals 55 and 56.
(analog input).
• System pump controlled by BMS or The Touchscreen Control.
NOTE: This drawing is a schematic
representation of a piping style and is
not intended to be used as a working
installation drawing. Local code
requirements must be met.
NOTE: Domestic circulator MUST be sized for
both the indirect and the boiler.