Figure 12. Multiple Boilers, Variable Primary Space Heating with Individual Isolation Valves
Control:
Use outdoor reset to maintain building loop temperature. See
Section 8.C.3 on page 67.
Set System pump to AUTO, pump runs during space heating
when outdoor temperature is below warm weather shutdown.
Place jumper on T-T for constant heating call; or interrupted if
so desired.
System sensor required for cascade, outdoor reset operation
and connected to Lead boiler; place sensor in common header
6 pipe diameters from last connected unit. See Section 8.D.3
on page 73
System pump controlled by The Touchscreen Control. Boiler
pump(s) not used.
Pump operation congurable in pump conguration menu. See
Section 8.D.5 on page 83.
Quick connect isolation valves, controlled by The Touchscreen
Control, are available from and required for 3+ boiler systems.
See Section 8.D.4 on page 74.
BMS control:
For Modbus/BACnet BMS mapping, refer to Section 7.F on
page 44.
Enable/disable boiler via T-T terminals (49, 50) for space
heating.
To enable/disable boiler for DHW using an aquastat, use
terminals 53 and 54.
To enable/disable boiler for DHW using a sensor, use
terminals 39 and 40.
BMS can control ring rate or setpoint via terminals 55 and 56.
(analog input).
System pump controlled by BMS or The Touchscreen Control.
NOTE: This drawing is a schematic
representation of a piping style and is
not intended to be used as a working
installation drawing. Local code
requirements must be met.