Installation and Operation Instructions Document 1470 Installation and Operation Instructions for Brute MagnaTech FT ® Modulating and Condensing. 20:1 Turndown. Touchscreen Control Boiler Model BCFH1000 999 MBTU/h Model BCFH1500 1,500 MBTU/h Model BCFH2000 1,999 MBTU/h Model BCFH3000 3,000 MBTU/h FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot boiler installation and maintenance.
TABLE OF CONTENTS SECTION 1 G eneral Information SECTION 5 Boiler Piping 1.A Introduction................................................ 5 5.A Water Connections................................... 26 1.B Model Identification ................................... 5 5.B Cold Water Make-Up................................ 26 1.C Warranty..................................................... 5 5.C Freeze Protection..................................... 26 1.D Safety Notes............................
Section 8 (continued) 8.D Configuration..................................... 69 8.D.1 8.D.1.a 8.E.13 LMV........................................................ 102 CH (Central Heat) .................................. 69 8.F Messages and USB......................... 103 CH1 (Central Heat, One) ....................... 70 8.F.1 Messages............................................... 103 8.D.1.a.1 PID Low................................................... 71 8.F.2 USB Functionality................
Page 5 SECTION 1 General Information 1.A 1.B Introduction Model Identification Primary information regarding your unit can be found on the Rating Plate on the outside face of the right-side panel. This manual includes information which will help you to install, operate, and maintain the Bradford White MagnaTech high efficiency commercial boilers. Please read this manual completely before proceeding with the installation.
Page 6 1.D Safety Notes Safety Notes are used thoughout this manual to bring attention to the presence of hazards with various risk levels and to offer important information concering the life of this product. There are 3 basic types. 1 WARNING 2 CAUTION 3 Indicates an imminently hazardous situation which, if not avoided, can or will result in death or serious injury and can or will result in catastrophic property damage.
Page 7 WARNING Electrical Shock Hazard Electrical shock can cause severe injury, death or property damage. Disconnect the power supply before beginning installation or changing the wiring to prevent electrical shock or damage to the equipment. It may be necessary to turn off more than one power supply to disconnect. All electrical wiring is to be done in accordance with local codes, or in the absence of local codes, with: 1) The National Electrical Code ANSI/NFPA No. 70 - latest Edition, or 2) CSA STD.
MAGNATHE Page 8 Venting Venting nformation Information imensions 1.E Venting Dimensions & Sizing Model Model 1000 1000 1500 1500 2000 2000 3000 3000 Table 1.
1000 30.2 (76.7) 80.0 (203) 52.4 (133) 70.5 (179) 60.0 (152) 8.2 (20.9) 60.0 (152) 74.2 (188) 1500 30.2 (76.7) 80.0 (203) 52.4 (133) 70.5 (179) 60.0 (152) 7.8 (19.7) 60.3 (153) 74.2 (188) HERM FT -FT Dimensional Data NATHERM GNATHERM AGNATHERM -FTDimensional FT - Dimensional - Dimensional Data Data Data 2000 34.6 (87.9) 80.0 (203) 56.3 (143) 73.3 (189) 60.0 (152) 9.1 (23.0) 63.1 (160) 73.6 (187) Page 3000 34.6 (87.9) 80.0 (203) 56.3 (143) 75.
Page 10 1.G Unit Overview Pressure Transmitters Blower Heat Exchanger Control Panel On all models, the Control Panel hinges forward for easy access to wiring and to the heat exchanger. Gas Supply Connection Water Outlet Field Electrical Connections High Voltage Panel Field Connections Main Power Connections NOTE: Field Wiring and Main Power Wiring should only enter at the rear of the boiler and at these electrical boxes. The top covers must remain removable for routine service. See Section 7.
Page 11 1.H Gas Train Components The Gas Train for all sizes has the same general layout. The only difference between them is the size of the components and piping.
Page 12 1.I Unpacking and the Install Kit This unit is shipped in a single crate. Carefully disassemble the crate and inspect the unit for any damage during shipping. Included in the crate and yet outside of the unit is the ‘Installation Kit’ box. Inspect the contents of the the Installation Kit box, making sure that all parts are included and not damaged. 1. Gromet, Nylon. 2. Box containing Outdoor Sensor 3. Box containing System Sensor 4. Tank Sensor 5.
Page 13 1.K Clearances 24” is required at Top to service the unit. Rear Top Panel is an access panel for the servicing of the Ignitor and Flame Rod. 11” / 24” at back of unit. Min” / Suggested 3” / 12” 3” Max 3” / 12” 18” / 24” Figure 3.
Page 14 SECTION 2 Venting and Combustion Air 2.A General Venting Information WARNING Selection of improper vent materials for installations that are installed in closets, or will be operated in high ambient temperature levels, may lead to property damage, personal injury, or death. WARNING Failure to use the appropriate vent material, installation techniques, or glues and sealants could lead to vent failure causing property damage, personal injury or death.
Page 15 a tee with the branch connection sized to allow for insertion of a flue gas analyzer probe. The branch connection must be resealable with a cap or other means to ensure the vent system remains sealed. (See Figure 4) Consideration must be given to the placement and orientation of the flue gas sampling port to ensure that condensate is free to flow back into the unit and not collect anywhere in the vent system - including in the flue gas sampling port. 2.B.1.b Exhaust Vent Terminal Figure 4.
Screen for horizontal PVC air pipe CA012004 CA012001 CA012001 CA012002 CA012003 CA012003 Screen for horizontal polypropylene air pipe CA012200 CA012201 CA012201 CA012202 CA012203 CA012203 D2012203 CA012603 CA012403 CA012403 Screen for vertical galvanized air pipe Page Screen 16 for vertical polypropylene air pipe D2012204 D2012201 D2012201 D2012202 CA012604 CA012601 CA012601 CA012602 D2012203 CA012603 Table 3a - Ducted Air Accessories Installation Standards Material United Stat
Page 17 2.C.1 2.C.2 Category lV Vent Sizes Non-positive pressure vent systems are generally vertically terminated. Table 10 gives guidelines for vent and air pipe sizes. Positive pressure vent systems may be either horizontally or vertically vented. The vent pipe used must be suitable for positive pressure. Table 10 shows the pipe size and allowable maximum equivalent of piping allowed for both air and vent in a Category lV system.
Page 18 2.C.4 Common Vent Test NOTE: This section does not describe a method for common venting this unit. It describes what must be done when an unit is removed from a common vent system. This unit requires special vent systems and fans for common vent. Contact the factory or your factory representative if you have questions about common venting this unit.
Page 19 2.C.5 Combustion Air Boilers must have provisions for combustion and ventilation air in accordance with the applicable requirements for Combustion Air Supply and Ventilation in the National Fuel Gas Code, ANSI Z223 1; or in Canada, the Natural Gas and Propane Installation Code, CSA B149.1. All applicable provisions of local building codes must also be adhered to. This unit can take combustion air from the space in which it is installed, or the combustion air can be ducted directly to the unit.
Page 20 2.C.5.b Ducted Combustion Air The combustion air can be taken through the wall, or through the roof. The manufacturer offers accessories to use with ducted air systems, as shown in Table 9. See Table 8 to select the appropriate diameter air pipe. When taken from the roof, a field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water. (See Figure 7).
Page 21 *When vent terminal is less than 10 feet (3 m) horizontally from a forced air inlet, the terminal must be at least 3 feet (0.9 m) above the air inlet. (US only) U.S. Installations (see note 1) Canadian Installations (see note 2) A= Clearance above grade, veranda, porch, deck, or balcony 12 inches (30 cm) See note 6 12 inches (30 cm) See note 6 B= Clearance to window or door that may be opened Direct vent only: 12 inches (30 cm); Other than Direct vent: 4 ft (1.
Page 22 Multiple Vents 2” Min. (Typ) Window OUTLET Multiple Air Intakes 2” Min. (Typ) 84” 36” 90 12” 213 INLET 12” Figure 6. 2.D.2 Above expected snow line Terminals must be placed such that they are a Minimum of 12” above the expected snow line. Local codes may have more specific requirements and must be consulted. Refer to the NFPA 54 National Fuel Gas Code and your local codes for all required clearances for venting.
Page 23 (Place in section 3.5) Model 1000 Model 1500 Model 2000 Model 3000 Air intake screen for unit placed outdoors CA011904 CA011901 CA011901 CA011901 Vent terminal for unit placed outdoors CA017201 CA017202 CA017202 CA017203 Table 11. Air & Vent Accessories for units placed outdoors Table 3** - Air & Vent Accessories for Units Placed Outdoors 2.E Outdoor Installation This unit may be installed indoors or outdoors.
Page 24 SECTION 3 Gas supply and Piping 3.A Gas Supply and Piping All Installations must conform to the National Fuel Gas Code ANSI Z223.1/NFPA54, and/or local codes. In Canada, the installation must conform to the latest edition of CSA B149.1 Natural Gas and Propane Gas Installation Code, and/or local codes. Gas piping should be supported by suitable hangers or floor stands, not the unit. Review the following instructions before proceeding with the installation. 1.
Page 25 4.B SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC Natural GRAVITY NATURAL GAS Gas Pipe SizeW.C. (in.) @ 0.50” NOMINAL PIPE SIZE PRESSURE DROP Nominal: Actual ID: Length (ft) 10 20 30 40 50 60 70 80 90 100 125 150 175 200 150 300 350 400 2” 2½” 3” 4” 5” 2.067” 2.469” 3.068” 4.026” 5.
Page 26 SECTION 5 Boiler Piping 5.A Boiler Water Connections NOTE: This unit must be installed in a closed pressure system with a minimum of 12 psi (82.7 kPa) static pressure at the boiler. The water piping should be supported by suitable hangers or floor stands. Do not support the piping with this unit. The hangers used should allow for expansion and contraction of pipe. Rigid hangers may transmit noise through the system resulting from the piping sliding in the hangers.
Page 27 5.D Suggested Boiler Piping Schematics On innitial installations, drain and flush the system before adding propylene glycol. Sludge and other sediments in the boiler can inhibit flow, resulting in rapid breakdown of glycol. Check the propylene glycol concentration annually. Add more water or propylene glycol as needed. This boiler is a high efficiency appliance.
Figure 9. Single Boiler, P/S Piping for Space Heating with P/S for Indirect Tank • System, boiler and DHW pumps controlled by BMS or The Touchscreen Control. • BMS can control firing rate or setpoint via terminals 55 and 56. (analog input). • To enable/disable boiler for DHW using a sensor, use terminals 39 and 40. • To enable/disable boiler for DHW using an aquastat, use terminals 53 and 54. • Enable/disable boiler via T-T terminals (49, 50) for space heating. (Section 8.D.2).
• System, boiler and DHW pumps controlled by BMS or The Touchscreen Control. • BMS can control firing rate or setpoint via terminals 55 and 56. (analog input). • To enable/disable boiler for DHW using a sensor, use terminals 39 and 40. • To enable/disable boiler for DHW using an aquastat, use terminals 53 and 54. • Enable/disable boiler via T-T terminals (49, 50) for space heating. • For Modbus/BACnet BMS mapping, refer to Section 7.
• System, boiler and DHW pumps controlled by BMS or The Touchscreen Control. • BMS can control firing rate or setpoint via terminals 55 and 56. (analog input). • To enable/disable boiler for DHW using a sensor, use terminals 39 and 40. • To enable/disable boiler for DHW using an aquastat, use terminals 53 and 54. • Enable/disable boiler via T-T terminals (49, 50) for space heating. • For Modbus/BACnet BMS mapping, refer to Section 7.
• System pump controlled by BMS or The Touchscreen Control. • BMS can control firing rate or setpoint via terminals 55 and 56. (analog input). • To enable/disable boiler for DHW using a sensor, use terminals 39 and 40. • To enable/disable boiler for DHW using an aquastat, use terminals 53 and 54. • Enable/disable boiler via T-T terminals (49, 50) for space heating. • For Modbus/BACnet BMS mapping, refer to Section 7.F on page 44.
Figure 13. Multiple Boilers, P/S Piping for Space Heating and simultaneous DHW heating w/ parallel piped single boiler • System pump controlled by BMS or The Touchscreen Control. • BMS can control firing rate or setpoint via terminals 55 and 56. (analog input). • To enable/disable boiler for DHW using a sensor, use terminals 39 and 40. • To enable/disable boiler for DHW using an aquastat, use terminals 53 and 54. • Enable/disable boiler via T-T terminals (49, 50) for space heating.
Figure 14. Multiple Boilers, P/S Piping for Space Heating with redundant P/S for Indirect Tank • System pump controlled by BMS or The Touchscreen Control. • BMS can control firing rate or setpoint via terminals 55 and 56. (analog input). • To enable/disable boiler for DHW using a sensor, use terminals 39 and 40. • To enable/disable boiler for DHW using an aquastat, use terminals 53 and 54. • Enable/disable boiler via T-T terminals (49, 50) for space heating.
Page 34 5.E DHW Heating The MagnaTech FT must not be used as a direct domestic (potable) water heater. It can be connected to an indirect water heater or heat exchanger to generate domestic (potable) hot water and the boiler’s controller includes indirect water heating logic. Examples of piping arrangements for indirect domestic water heating can be found in Section 5.D.
Page 35 This page intentionally left blank
Page 36 SECTION 6 Condensate Drain Trap This appliance creates condensation as a by-product of high combustion efficiency. The condensate must be drained from unit and from the vent system. A combination condensate drain trap is included with the unit for on-site assembly. This condensate drain trap must be installed to prevent the accumulation of condensate. Connect a ¾” PVC pipe between the drain connection and a floor drain.
Page 37 Document 4378 Commercial FT, Condensate Trap Assembly Instructions 1. The discharge hose 'end adapter'. 2. Hose adapter. 3. Hose clamps (3). 4. Transparent discharge hose. 5. The condensate trap (pre-assembled with cap & float). 6. Inlet Hose, 2.5" x .75". 3 7. Adapter, .75" barb x 1.0" NPT, PVC. 8. Mounting bracket (top half). 9. Mounting bracket (bottom half) with the velcro strap. 10. Screws (2).
Page 38 SECTION 7 Electrical Connections 7.A Installation Warnings CAUTION The supply voltage to this unit must not be disconnected, except for service or isolation, or unless otherwise instructed by procedures outlined in this manual. To signal a call for heat, use the heat demand inputs, as shown in the wiring diagram. DO NOT MAKE AND BREAK THE LINE VOLTAGE TO THE UNIT TO SIGNAL A CALL FOR HEAT. A call for heat/end call for heat MUST be connected to the heat demand terminals.
Electrical Data Page 39 Flex Conduit for Field Wiring Field Electrical Connections at the Terminal Block on the Control Panel Hinged Control Panel swings open for servicing and setup Low Voltage Box for Field Connections High Voltage Box for Main Power Connections Available Knockouts for other wiring needs VIEW from the BACK NOTES: Field Wiring and Main Power Wiring should only enter at the rear of the boiler and at these electrical boxes. The top covers must remain removable for routine service.
Page 40 7.D Control Panel Layout LMV Controller Assembly Handset, Display and Operating Unit. For Certified and Trained Field Techs Only. Low Water Cut-Off 12 Volt DC Power Supply Linc Controller Assembly Field Connections Terminal Block 70 66 69 65 68 64 BMS A 63 CASCADE RS485 BMS GND 62 CASCADE GND 67 61 ANALOG ANALOG RUN RELAY ALARM RELAY INPUT OUTPUT CONTACTS CONTACTS BMS B 60 CASCADE B CASCADE A 59 ALARM - N.C. ALARM - N.O. RUN - N.O.
Page 41 maximum. DHW pump functionality is configured using the touch screen. System Pump - If connecting a system pump, use terminals 29 and 30. As this is a dry contact, the system pump supply voltage or system pump relay coil voltage would be applied at terminal 29, and when the system pump is activated, power will be available at terminal 30. Contact ratings are 250VAC, 1.5A maximum. System pump functionality is configured using the touch screen. Isolation Valve – See Section 7.E.
Page 42 NOTE: When running the Power and Field Connection wires (Lead Lag, System Sensor, Outdoor Sensor, Building Automation, etc.), it is helpful to exit and enter the units through the lower back panels so that during future servicing, the wires do not interfere with the removal of the panels. AVIS: Lors de l’exécution de la puissance et des câbles de raccordement (câble de capteur du système, Lag, capteur Extérieur, domotique, etc.
Page 43 Figure 22. Jumper locations at the inputs 7.E.9 RS 485 for Cascade (Lead Lag) Cascade - Prior to wiring units for cascade operations, select one unit as the lead boiler. Other units connected to the lead boiler will be referred to as lag units. Communication between lead and lag units is accomplished using RS485. When wiring these units for cascade operations, use terminals 65, 66, and 67 (See Figure 20 on page 40). Use 2-wire twisted pair, shielded w/drain (communication cable) between units.
Page 44 7.
Page 45 Modbus Address Type R/W Map Descriptor Name BACnet BACnet Data Type Object ID R/W 37 S16 Read LMV_Phase AI 37 Read 38 39 40 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 U16 U16 U16 U16 U16 S16 S16 S16 U16 U16 U16 S16 S16 S16 S16 U16 U16 U16 U16 U16 U16 Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read History ‐ DHW Demand Cycles History ‐ CH1 Demand Cycles History ‐ CH2 Demand Cycles History ‐ Cascade Demand Cycles Histo
Page 46 7.
Page 47 Modbus Address Type R/W Map Descriptor Name BACnet BACnet Data Type Object ID R/W 84 U16 Read Burner Status 1 AI 84 Read 85 86 87 88 U16 U16 U16 U16 Read Read Read Read LMV ‐ Lower Trim Limit LMV ‐ Upper Trim Limit LMV ‐ Current Trim LMV ‐ Fan Speed AI AI AI AI 85 86 87 88 Read Read Read Read 89 U16 Read Boiler Pump Status AI 89 Read 90 U16 Read Cascade Master Heat Demand AI 90 Read 91 92 93 94 95 96 97 98 99 U16 U16 U16 U16 U16 U16 U16 U16 U16 Read Read Read Read
Wire Color Legend BK Black BL Blue BR Brown G Green GY Grey Orange O Pink P Red R W White V Violet Y Yellow BK MAIN POWER SWITCH Figure 23. Wiring Diagram, Models 1000 - 3000 RUN RELAY CONTACTS Analog Output Analog Input 31 32 33 34 35 36 37 38 VALVE ALARM BELL SYSTEM SUPPLY SYSTEM RETURN 45 46 47 48 PROOF OF CLOSE PROOF OF OPEN C N.C. N.O. 63 64 58 0-10VDC N.O. 57 PUMP 62 56 BMS 0-10VDC 61 55 DHW C 54 DHW N.C.
3 2 1 PRESSURE TRANSMITTER - 2 3 2 1 PRESSURE TRANSMITTER - 1 R W/R BK R W/BN BK 9 1 11 3 12 4 13 5 14 6 15 7 BK/O BR/Y BR/Y X4-4 X4-2 X4-12 X4-7 X4-17 X4-14 See TB1-44 BR/R X4-1 X4-11 X4-6 X4-16 X4-5 X4-15 X4-8 X4-18 X4-3 X4-13 X4-9 X4-19 See TB1-43 GY/R GY/BK R GY/R GY/V R BL/W BL BR/R BK/W W/R X1-14 X1-2 X1-13 X22-1 X22-9 X22-2 X22-8 X22-11 X22-12 X22-7 X3-14 X3-6 BR/G W/G R P G TB1-7:2 120N BK W DOCUMENT# H2406700 6 7 6 7 6 7 8 45 46
Figure 24.
Figure 25.
FIELD CONN- Figure 26.
V P Figure 27.
Page 54 7.
N 4 3 2 PRESSURE TRANSMITTER - 1 1 2 3 X22-2 PRESSURE TRANSMITTER - 2 1 2 3 X22-1 PWM SIGNAL BIC (continued) X21-1 X9-1 BLOWER 3 1 T 1 2 3 4 TB1-120L X3-04-5 TB1-120N X3-04-4 TB1-GND X3-04-3 POWER SWITCH 5 LMV BURNER CONTROLLER 6 7 8 CONTROLLER POWER 9 10 11 X3-04-2 TERMINAL STRIP 120VAC X3-04-1 BLOWER CONTACTOR 12 13 SAFETY CHAIN IS SATISFIED 14 15 X5-03-4 16 X5-03-2 X5-03-1 24VAC TRANSFORMER 17 18 HEAT DEMAND FROM BOILER CONTROLLER 19 20 X3-05-1 TERMINAL STRIP 24VAC
Page 56 1 2 LMV BIC 208/240VAC (1PH/60Hz) L1 L2 X64-4 X64-3 X64-2 Ladder Diagrams (continued) X22-7 7.
Page 57 4 3 2 PWM SIGNAL BLOWER PRESSURE TRANSMITTER - 1 1 2 3 X22-2 PRESSURE TRANSMITTER - 2 1 2 3 X22-1 BIC (continued) X21-1 3 X9-1 120VAC TRANSFORMER TB1-120L X3-04-5 TB1-120N X3-04-4 TB1-GND X3-04-3 LMV BURNER CONTROLLER CONTROLLER POWER X3-04-2 POWER SWITCH X3-04-1 TERMINAL STRIP 120VAC X5-03-4 VFD CONTACTOR X5-03-2 X5-03-1 24VAC TRANSFORMER SAFETY CHAIN IS SATISFIED Power Outputs X5-01-2 BOILER PUMP (NOT INCLUDED) P 12 13 12 14 12 15 2 16 2 17 2 18 2 2
Page 58 2 X64-4 X64-3 X64-2 BIC 208/480 (3PH/60Hz) L1 L2 L3 LMV 1 Ladder Diagrams (continued) X22-7 7.
4 3 LMV 2 PWM SIGNAL PRESSURE TRANSMITTER - 1 1 2 3 X22-2 PRESSURE TRANSMITTER - 2 1 2 3 X22-1 BIC (continued) 5 0N 4N BLOWER 7 8 4 5 6 120VAC TRANSFORMER TB1-120L X3-04-5 TB1-120N X3-04-4 TB1-GND X3-04-3 LMV BURNER CONTROLLER 9 10 11 12 POWER SWITCH 13 X3-04-1 TERMINAL STRIP 120VAC X5-03-4 VFD CONTACTOR X5-03-2 X5-03-1 24VAC TRANSFORMER 14 SAFETY CHAIN IS SATISFIED 15 16 17 18 19 HEAT DEMAND FROM BOILER CONTROLLER 20 21 X3-05-1 TERMINAL STRIP 24VAC 22 X3-02-1 Pow
1 2 600 (3PH/60Hz) L1 L2 L3 CB X64-4 X64-3 X64-2 BIC Ladder Diagrams (continued) X22-7 7.
4 3 LMV 2 X64-4 X64-3 X64-2 Page 61 PWM SIGNAL PRESSURE TRANSMITTER - 1 1 2 3 X22-2 BLOWER PRESSURE TRANSMITTER - 2 1 2 3 X22-1 BIC (continued) 4 5 X21-1 3 X9-1 120VAC TRANSFORMER TB1-120L X3-04-5 TB1-120N X3-04-4 TB1-GND X3-04-3 LMV BURNER CONTROLLER CONTROLLER POWER X3-04-2 POWER SWITCH 120N X3-04-1 TERMINAL STRIP 120VAC X5-03-4 VFD CONTACTOR X5-03-2 X5-03-1 24VAC TRANSFORMER -24N SAFETY CHAIN IS SATISFIED HEAT DEMAND FROM BOILER CONTROLLER X3-05-1 TERMINAL STRIP 24VA
Page 62 SECTION 8 Control Operation 8.A The Home Screen CSP: is the Calculated (and Current) Set Point. It can be based on the CH1 (Central Heat One), CH2, or the DHW (Domestic Hot Water) setpoint, depending on the model and the installation set up and may be adjusted by the Outdoor Reset and the DHW Offset. 8.A.1 Name Security Home Screen Active Icons Icon Description Displays the current lock status icon. Touch the lock icon to lock or unlock the Touchscreen Display. See Section 8.
Page 63 8.A.2 Keypad Operations NOTE: You can always tell exactly where you have navigated to by looking at the icons in the Navigation Bar. In this example you are in Home / Configure / Central Heat / Central Heat One Shows the current setting of the Parameter. These windows will reflect the allowable ranges of the parameter To delete the current setting before entering in the new value. “Up and Down” arrows are used to increment the setting accordingly.
Page 64 8.B Login to Lock / Unlock the Display Screen Password Protection: To change configuration or parameters, a password is required. The control system includes three levels of password protection. Touch the 'Current Lock Status' icon at the top of the screen. 1- U SER password is lhs. This password is for ‘Safe’ access ‘Non-Critical’ adjustments and functions. Use this password if you want to make adjustments without fear of altering the critical configuration of the system.
Q U I C K S TA R T 8.C Page 65 Quick Start Quick Start will allow a user to configure the BASIC functionality of the control, without going through all of the parameters that are available. The 6 BASIC functionalites at Quick Start are • Central Heat, • Domestic Hot Water, • Outdoor Reset, • Warm Weather Shutdown, • Anti-short Cycle and • Time & Date 8.C.1 CH (Central Heat) ”CH” stands for “Central Heat.” It is used for space heating demands.
Page 66 8.C.1.a CH1 (Central Heat, One) Q U I C K S TA R T 1 • Enable/Disable – This allows CH1 to be enabled/disabled. The default setting is Enabled. • Set Point – This is the set point temperature. 8.C.1.b CH2 (Central Heat, Two) 2 To navigate to the CH2 Quick Start Screen, touch the CH2 Icon on the CH Quick Start Selection Screen. The CH2 screen will be have the same look and functionality as the CH1 Screen. 8.C.2 DHW (Domestic Hot Water) ”DHW” stands for “domestic hot water.
Q U I C K S TA R T Page 67 8.C.3 Outdoor Reset Outdoor reset adjusts a boiler’s setpoint based on outdoor air temperature. This is for boilers only, and is not used for domestic water. To navigate to the Outdoor Quick Start Screen, touch the Outdoor Icon on the Quick Start Screen. The Outdoor Quick Start Screen allows the adjustment of the following parameters: • Enable/Disable – Enables and disables the outdoor reset functionality.
Q U I C K S TA R T Page 68 8.C.5 Anti-Short Cycle To navigate to the Anti-Short Cycle Quick Start Screen, touch the Anti-Short Cycle Icon on the Quick Start Screen. The Anti-Short Cycle Quick Start Screen allows adjustment of the following parameter: • C ycle Time – The amount of time after a heat demand is satisfied that the unit will wait to satisfy the next active heat demand. NOTE: Anti-Short Cycle Time does not apply to DHW heat demands.
C O N F I G U R AT I O N 8.D Configuration This area of the controller allows access to all parameters available, based on the access level that is unlocked. To navigate to the Configuration Screen, touch the Configure Icon in the lower left portion of the Home Screen. CSP: is the Calculated (and Current) Set Point.
C O N F I G U R AT I O N Page 70 8.D.1 CH (Central Heat) “CH” stands for “Central Heat.” It is used for space heating demands. On the Configure Screen, touch the CH thermometer icon to navigate to the CH Selection Screen There are two identical heat demands, CH1 and CH2, each with independent control algorithms and independent inputs on the input terminal strip, see 7.E.6 on page 42 From the CH Selection Screen, touching CH1 navigates to the CH1 Parameters Menu. 8.D.1.
C O N F I G U R AT I O N 8.D.1.a.1 PID Low Note that in most cases, PID parameters will not need to be changed. The PID Parameters Screen allows adjustment to the following parameters: • P roportional Gain – This value is the corrective action that is proportional to the error (set point – control temperature). • I ntegral Time – This value is applied to the sum of the error over a period of time. • D erivative Time – This value is applied to the rate of change of the error.
Page 72 8.D.2 DHW (Domestic Hot Water) To navigate to the DHW Screen, touch the DHW faucet icon on the Configure Screen. DHW has all the same parameters as CH1 and CH2 with one exception. DHW has the following additional parameters for adjustment: • D HW Offset – Upon a DHW heat demand, the unit will control the outlet temperature to the DHW Set Point plus the DHW Offset (set point + DHW Offset).
C O N F I G U R AT I O N 8.D.3 Page 73 Outdoor Reset Outdoor reset adjusts a boiler’s setpoint based on outdoor air temperature. This is for boilers only, and is not used for domestic water. The Outdoor Parameters Screen allows the adjustment of the following parameters: • Enable/Disable – Enables and disables the outdoor reset functionality. • M aximum Outdoor Temperature – The outdoor temperature at which the unit will start using the minimum water temperature as the set point.
Page 74 8.D.4 Cascade (All about Lead / Lag) An installation with two or more units may be configured for cascade operation. Up to eight units can be cascaded and controlled together. To navigate to the Cascade Screen, touch the Cascade Icon on the Configuration Screen. The Cascade Screen provides four navigation icons to configure the system for cascade operations. These navigation icons are: • C ascade – This icon navigates to the Cascade Parameters screen for hydronic boiler cascade operations.
C O N F I G U R AT I O N Log In Parameter User Page 75 Settings Installer OEM Min Max Default Unit Base Load X X 40 100 65 % Drop Load X X 20 100 20 % Min On Time X X 30 600 60 Seconds Min Off Time X X 30 600 30 Seconds Table 19. Parameter Settings minimum (instead of the allowable minimum firing rate of 5%).
Page 76 As the load increases: As the load decreases: • Until all units are firing, no unit is requested to exceed the base load value. • As long as all units are firing – the base load value can be exceeded, as long as all units maintain the same firing rate. • Additional units are added once the Base Load Value has been reached and the Min On Time timer has expired.
C O N F I G U R AT I O N Page 77 About Cascading (Lead / Lag) -continued Low demand: The first boiler in sequence ignites and gradually increases firing rate to satify the heat demand.
eight boilers reach the Base Load Value , all units are allowed to increase firing rate (same at all boilers) up to Page 78 maximum firing rate. Decreasing demand: As the demand decreases, once the requested firing rate reaches the Drop Load Value , the eighth boiler turns off. Continued decreasing demand: As the demand decreases, once the requested firing rate reaches the Drop Load Value , the seventh boiler turns off.
C O N F I G U R AT I O N Page 79 8.D.4.a Cascade Parameters To navigate to the Cascade Parameters Screen, touch the Cascade Icon on the Configuration Screen, then touch the Cascade Parameters Icon. The Cascade Parameters Screen allows adjustment of the following parameters: • A ddress – When manually addressing each boiler for cascade operations, this parameter is used to set the local boiler address. Each boiler must have a unique address. A boiler with a value of 1 is the lead boiler.
C O N F I G U R AT I O N Page 80 8.D.4.a.1 Base / Drop Load Base Load – Is the firing rate that must be achieved prior to adding another unit to satisfy the heat demand. Drop Load – A s the demand for heat decreases, this is the firing rate that units turn off. The last unit to fire is the first to get turned off. Min On Time – As the demand for heat increases, this is the delay time prior to firing additional units.
C O N F I G U R AT I O N Page 81 8.D.4.b Rotation To navigate to the Cascade Rotation Screen, touch the Cascade Icon on the Configure Screen, then touch the Rotation Icon on the Cascade Configuration Screen. The Cascade Rotation Screen is a view only screen. This screen indicates how many units are connected in a cascade configuration, the order in which each unit will run, and the percent at which each unit is running.
C O N F I G U R AT I O N Page 82 8.D.4.c Redundancy To navigate to the Cascade Redundancy Screen, touch the Cascade Icon on the Configuration Screen, then touch the Redundancy Icon on the Cascade Configuration Screen. The Cascade Redundancy Screen allows the selection of one of three options for redundancy in cascade systems.
C O N F I G U R AT I O N Page 83 8.D.5 Pumps The Pump Configuration Screen allows adjustment of the following 7 parameters: • Boiler Pump Control – This parameter provides the ability to set the boiler pump functionality to be: Auto – t he pump will turn on automatically upon a call for heat. Always On – the pump will run continuously. Off Dur ing DHW – the pump will not turn on during a DHW heat demand.
Page 84 C O N F I G U R AT I O N 8.D.5.a Variable Speed Pump Control The Variable Speed Pump Control Screen allows the adjustment of the following parameters: • O n Delay – Upon a call for heat, once the unit ignites, this is the amount of time the unit will wait prior to modulating the pump speed. • P roportional Gain – This value is the corrective action that is proportional to the error (Set Point – Control Temperature).
C O N F I G U R AT I O N Page 85 8.D.7 Temp Limits To navigate to the Temp Limits Screen, touch the Temp Limits Icon on the Configuration Screen. The Temp Limits Configuration Screen allows adjustment of the following parameters: • A uto Reset CH– The temperature at which the unit will shut down when outlet temperature exceeds its maximum auto reset set point. The control will automatically reset, based on the reset differential.
Page 86 C O N F I G U R AT I O N 8.D.7.b Flue Limitation Parameters To navigate to the Flue Limitation Parameters Screen, touch the Temp Limits Icon on the Configuration Screen, then touch the Flue Limitation button on the Temperature Limits Parameters Screen. The Flue Limitation Parameters Screen allows adjustment of the following parameters: • M anual Reset Flue – The temperature at which the unit will shut down due to exceeding a flue temperature manual reset condition.
C O N F I G U R AT I O N Page 87 8.D.8 External The External Configuration Screen applies to the 0-10VDC (4-20mA) analog input BAS signal, and allows adjustment of the following parameters: To navigate to the External Configuration Screen, touch the External Icon on the Configuration Screen. • C ontrol Mode – This parameter provides the ability to either disable external control or configure the unit for Boiler Set Point or Firing Rate control mode.
C O N F I G U R AT I O N Page 88 8.D.8.a External – Remote Set Point External (0 – 10VDC or 4 – 20mA) • A n External heat demand can be initiated by a Building Automation System (BAS) using a 0-10VDC or 4-20mA signal. This input can be configured for Remote Set Point or Remote Firing Rate operations. • W ith Remote Set Point selected, the unit will initiate a heat demand once the analog input signal exceeds the Demand On value.
C O N F I G U R AT I O N Page 89 8.D.8.b External Firing Rate With External Firing Rate selected, the unit will initiate a heat demand once the analog input signal exceeds the Demand On value. Once the demand is initiated, the analog input signal must be lower than Demand Off to remove the heat demand. The external analog signal will activate stages as shown in Figure 40.
Page 90 C O N F I G U R AT I O N 8.D.10 Miscellaneous Features To navigate to the Miscellaneous Features Screen, touch the Miscellaneous Features Icon on the Configuration Screen. The Miscellaneous Features screen provides navigation for the following items: • P riorities – To set the Demand Priorities for all configured CHW or DHW heating demands. The higher the number, the higher the priority it is assigned. • A nti-short Cycle – To navigate to the Anti-short Cycle Configuration Screen.
C O N F I G U R AT I O N Page 91 8.D.10.a Demands Priorities To navigate to the Demands Priorities Screen, first go to the Miscellaneous folder. At the Demands Priorities screen select each configured demand and assign a priority number. Remember to always save the new setting with the button. 8.D.10.
Page 92 C O N F I G U R AT I O N 8.D.10.c Warm Weather To navigate to the Warm Weather Configuration Screen, touch the Miscellaneous Features on the Configuration Screen, then touch the Warm Weather Icon on the Miscellaneous Features screen. The Warm Weather Configuration Screen allows adjustment of the following parameters: • T emp Min – Upon an active warm weather shutdown condition, this is the temperature at which the unit will reset the shutdown condition to satisfy a heat demand.
C O N F I G U R AT I O N Page 93 8.D.10.d COM Port, BMS The control has Modbus and BACnet MSTP (RS485) protocols on board, for use with Building Management Systems. Gateways can be used for other communication protocols. To navigate to the COM Port Configuration Screen, touch the Misc Icon on the Configuration Screen, then touch the COM Port Icon on the Misc Configuration Screen.
Page 94 C O N F I G U R AT I O N 8.D.10.e Temperature Conversion To navigate to the Temperature Conversion Configuration Screen, touch the Temperature Conversion Icon on the Miscellaneous Features screen. The Temperature Conversion Configuration Screen allows adjustment of the following parameter: • Conversion unit – This parameter can be set to Fahrenheit or Celsius. 8.D.10.
C O N F I G U R AT I O N 8.D.10.g Trim Page 95 (O2 Trim Enable / Disable) To navigate to the Trim Menu, touch the Trim Icon on the Miscellaneous Menu Screen. This O2 Trim Menu allows you to • Enable/Disable NOTE: All Service Options for O2 Trim are available only with the OEM Login. 8.D.10.h Isolation Valve To navigate to the Isolation Valve Menu, touch the Isolation Valve Icon on the Miscellaneous Menu Screen.
Page 96 Isolation Valve - Single Boiler Operation 1. Disabled – if the isolation valve functionality is disabled, via the display, the isolation valve output will not actuate, and the boiler will ignore the status of the limit switch inputs. 2. Enabled – if the isolation valve functionality is enabled (default setting), the following will occur: i. Upon a heat demand, the valve will open.
Page 97 open, to avoid dead heading the system pump. Additional isolation valves may also be open, based on the value of “Min. # of Open Valves”. vi. As the cascade rotation functionality rotates which boiler fires first to satisfy a heat demand, the open limit switch of the new boiler that will fire first must be open prior to closing the isolation valve of the previous boiler that was in the sequence to fire first. In addition, if the value of “Min.
Page 98 8.E SERVICE Service Screens To navigate to the Service Screen, touch the Service Icon in the lower left portion of the Home Screen. Available only to the factory or technician qualified at the OEM level. 8.E.1 Burner Navigate to the Burner Screen by touching the Burner Button on the Service Screen.
SERVICE Page 99 8.E.2 Digital I/O ( Input / Output ) There are two screens associated with the Digital I/O: Digital I/O Screen-Inputs; Digital I/O Screen-Outputs. Navigate to the Digital I/O Screen by touching the Digital I/O Button on the Service Screen. Digital I/O Inputs: The indicator light associated with the input is green when the input is satisfied. For example, if there is adequate flow, the flow switch is satisfied, and the flow switch digital input indicator light is green.
SERVICE Page 100 8.E.3 Analog I/O Navigate to the Analog I/O Screen by touching the Analog I/O Button on the Service Screen. There are two screens associated with the Analog I/O: Analog I/O Inputs; Analog I/O Outputs. Analog I/O Input: There are three types of analog inputs; temperature sensors, flame signal, and voltage/current (VDC/ mA). Wiring of these inputs are covered in SECTION 7 NOTE: If the input is not attached, the value will be zero.
SERVICE Page 101 8.E.4 Screen Settings Timeout Navigate to Screen Settings by touching the Screen Button on the Service Screen. There are two adjustable screen settings: Light Timeout and AutoLock Timeout. • L ight Timeout allows the user to adjust the amount of time the touch screen backlight will remain lit after user interaction has ceased. • A utoLock Timeout allows the user to adjust the amount of time the touch screen will remain unlocked with no user interaction. 8.E.
SERVICE Page 102 8.E.7 Factory Reset Touching the Factory Reset Button on the Service Screen resets all touch screen adjustable parameters back to the factory default setting. 8.E.8 HMI Model OEM only 8.E.9 BIC Model OEM only 8.E.10 Both Model. OEM only. 8.E.11 About About the Firmware version of the touchscreen. 8.E.12 O2 (Trim Set Point) The O2 menu allows the Installer to adjust the Trim Set Point. 8.E.
Page 103 8.F Messages and USB 8.F.1 Messages Messages The ‘Messages’ icon at the bottom of the home screen displays an ‘Exclamation Point’ when messages are present. Press the icon to see the message(s). 8.F.2 USB Functionality The USB port is on the back of the display. To access it, open both panels and look for the black USB cable extending from the back of the display. See Figure 42. When the USB icon has appeared over the Message icon, press the USB icon to access the USB menu.
Page 104 8.G Active Demands The Active Demand Window indicates the status of active heat demands. Sec�on Ac�ve Demands A black heat demand icon6.5 indicates the heat demand that is currently being satisfied. A “greyed out” heat demand icon is either lower in priority than the heat demand that is currently being satisfied, or the heat demand has reached Ac�ve Demand Bar The Ac�ve Demand Bar indicates the status of ac�ve heat demands. A black heat demand icon set point, but remains active.
Page 105 SECTION 9 Parameter Tables NA NA NA NA NA Unit NA NA NA NA NA Unit NA NA NA NA NA Hour Hour Minute Minute MonthMonth Day Day Year Year xx xx xx xx xx xx xx xx xx xx x x x x x x xx x x x x x x xx xx xx xx xx xx xx xx x x x x x x x x Disable Disable 40 40 1 1 0 0 0 0 0 0 0 0 0 0 Enable Enable 210 210 5 5 20 20 20 20 10 10 10 10 10 10 Enable Enable 180 180 2 2 10 10 10 10 5 5 2 2 0 0 N/A N/A °F/C °F/C N/A N/A °F/C °F/C °F/C °F/C N/A N/A Seconds Seconds Seconds Seconds x xx x x x x x
Unit Unit Default Default Maximu m Maximu m Minimum Factory Minimum Factory OEM Installer User OEM Installer User Page 106 PumpPump Configuration Configuration Auto/ Auto/ Always On/ Off Always On/ Off Disable Disable DuringDuring DHW DHW 0 0 600 600 DisableAuto/ Auto/ Always Disable Always On On 0 0 600 600 Auto/ Auto/ Always On/ Off Always On/ Off Disable Disable DuringDuring DHW DHW 0 0 600 600 Auto Auto N/A N/A 60 60 Auto Auto 60 60 Seconds Seconds N/A N/A Seconds Seconds Auto Auto N/A
0 10 600 600 2000 2000 x xx x 1 1 240 240 x xx x x x x x x x x xx xx xx xx xx xx xx x x x x x x x x x x x x x xx xx xx xx xx xx x x x x x x x xx x xx xx xx xx x x x x 300 300 1440 1440 60 60 Unit 0 10 Unit x x Default xx xx Default Maximu m Maximu m x x Factory OEM Minimum Burner Burner Burner Burner Enable/Disable Enable/Disable Screen Screen Settings Settings Light Light Timeout Timeout x AutoLock AutoLock Timeout Timeout x Pressure Pressure a a b b c c Maximum Maximum
Page 108 SECTION 10 I nitial startup Instructions 10.A Filling the Boiler System 1. Ensure the system is fully connected. Close all bleeding devices and open the make-up water valve. Allow the system to fill slowly. 2. If a make-up water pump is employed, adjust the pressure switch on pumping system to provide a minimum of 12 psi (81.8 kPa) at the highest point in the heating loop. 3.
Page 109 10.B Initial Operation The initial setup must be checked before the unit is put into operation. Problems such as failure to start, rough ignition, strong exhaust odors, etc. can be due to improper setup. Damage to the boiler resulting from improper setup is not covered by the limited warranty. 10.B.1 Initial Burner Operation 1. Using this manual, make sure the installation is complete and in full compliance with the instructions and all local codes. 2.
Page 110 10.B.2 Combustion Setup Procedure Hi-Fire, Low-Fire The gas system must be set up properly, so the boiler will run efficiently throughout its modulation range under the installed conditions. This setup should only be performed by a factory trained technician. 1. S et up a gas pressure gage (monometer) on the incoming gas line. A test plug is provided on the back of the boiler gas line. If the gas pressure is greater than 10.5” w.c.
Page 111 Model Gas Type High-Fire CO2 All Models Natural 9.0% +/- 0.2% Low-Fire CO2 Maximum CO (ppm) Greater than 8.0% & less than 9.2% 50 Table 22. Combustion Settings. 8. I f needed, adjust the fuel pressure adjustment screw (See Figure 51) to obtain a Hi-Fire CO2 measurement of 9.0% +/- 0.2%. NOTE: Turn the adjustment screw only a quarter turn per adjustment either up or down, then watch the combustion analyzer for the result.
Page 112 10.C Shutting Down the Unit 10.E Controllers 1. Turn off the main electrical disconnect switch. 2. Close all manual gas valves. This unit utilizes three (3) separate controllers to manage system functions, burner management and air/ fuel ratio control: This step must be performed by a qualified service person. 3. If freezing is anticipated, drain the unit and be sure to also protect the building piping from freezing.
Page 113 10.F Transmitters This unit utilizes a pair of pressure transmitters to determine that the pressure drop across the combustion air/flue gas side of the system is within acceptable bounds for proper operation. If during operation the differential pressure across the system exceeds a predetermined value at a given firing rate, the system will shut down and a “Burner An Pressure Error” will be displayed.
Page 114 SECTION 11 Maintenance 11.A System Maintenance Do the following once a year: 1. Lubricate all the pumps in the system, per the instructions on the pump. 2. Inspect the venting system for obstruction or leakage. Periodically clean the screens in the vent terminal and combustion air terminal (when used). 3. Remove and inspect the air filter. Clean with soapy water if needed. Be sure that filter is dry before reinserting back into air filter box. Replace air filter if damaged. 4.
Page 115 installed the cables should be properly coiled and secured and reconnected to the LMV. In the event of failure of the on/off Honeywell solenoid, the entire valve must be replaced. Replacements solenoids are not available from Honeywell at this time. For the pressure regulating valve, the upper half of the valve may be replaced leaving the valve body in place. Care must be taken to replaced the fuel and air side sensing lines connected to the pressure regulator.
Page 116 11.B.7 Heat Exchanger Tubes Black carbon soot build-up on the internal surfaces of the heat exchanger is caused by one or more of the following: incomplete combustion, combustion air problems, venting problems or boiler short-cycling. Soot buildup or other debris on the heat exchanger may restrict the flue passages. If black carbon soot buildup on the heat exchanger is suspected, disconnect the electrical supply to the unit and turn off the gas supply by closing the manual gas valve on the unit.
Page 117 11.B.10 Oxygen Sensor The oxygen sensor is an automotive derived sensor which will require periodic replacement. If the sensor fails or is out of calibration the Oxygen and Carbon Monoxide lines on the main menu will blink red and dashes will be displayed instead of numeric values. Use only Mfgr supplied sensors as replacements and tighten the sensor into the fitting on the heat exchanger exhaust transition to 30 to 40 ft-lb of torque. HIGH LIMIT SWITCHES 11.B.
Page 118 SECTION 12 Troubleshooting 12.A Lockouts and Errors. Condition Flow Switch Low Water Cut Off Information • Insufficient flow at the outlet of the boiler/heater • Auto-reset Condition • Annunciation – “Warning Flow switch open” on Message Screen • Insufficient water level in the boiler/heater heat exchanger. • Manual-reset Condition • Annunciation – on Navigation Bar Corrective Action • Faulty boiler/heater pump – replace pump. • Faulty pump contactor – replace contactor.
Page 119 Condition Flow Switch Low Water Outlet Cut Off Drift Sensor or Flue Sensor Drift Manual Reset High Limit Information • Insufficient flow at the outlet of the boiler/heater • Auto-reset Condition • Annunciation – “Warning Flow switch open” on Message Screen •• Insufficient water levelreadings in the boiler/heater Dual element sensor do not heat exchanger. agree.
Page 120 12.B LMV Errors. In addition to the error messages displayed on the display unit, the LMV Status menu provides an Error Code and corresponding Diagnostic Code associated with failures of the LMV controller. The following table provides an abbreviated list of common LMV errors and corrective actions. For a complete listing of LMV errors please refer to the LMV Technical Instructions which can be found at Error Code List LMV http://www.scccombustion.
Page 121 Error Diag. Meaning for the LMV3 Corrective Action Code Code Note: Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes. 82 1 Timeout of standardization (VSD ramp down time too long) Standardization timed out because the VSD took too long to ramp down at the end of the standardization. Either decrease the ramp down time in the VSD or increase the setting of parameter 523.
Page 122 Error Diag. Meaning for the LMV3 Corrective Action Code Code Note: Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes. 83 No speed signal was detected. 1) Ensure that the motor is rotating. If it is not, check the wiring of the VSD / PWM blower. 2) If using a VSD, turn the motor by hand to ensure that the LED on the 16 Interruption of speed signal speed sensor lights up when it sees the speed wheel.
Page 123 Error Diag. Meaning for the LMV3 Corrective Action Code Code Note: Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes. 0 Position error 1 Line interruption 8 Curve too steep in terms of ramp rate 16 Step deviation in comparison with last referencing 86 86 Any # Error air actuator Check the wiring between the fuel actuator and LMV3 terminal X54. There should more > 0.
Page 124 SECTION 13 Replacement Parts Use only genuine Manufacturer replacement parts. To order or purchase parts, contact your nearest manufacturers dealer or distributor. (See the back cover of this manual for the manufacturers website). 13.
Page 125 ITEM NO. DESCRIPTION 1000 1500 2000 3000 PART NO. PART NO. PART NO. PART NO. R10T2000 R15T2000 R20T2000 R30T2000 1 HEAT EXCHANGER ASSEMBLY 2 LOW AIR PRESSURE SENSOR, SHINEUI E2389700 3 SENSOR, OXYGEN (LAMBDA), BOSCH LSU 4.9 E2376700 4 DISPLAY, TOUCH SCREEN, 7 IN DIAG, HTD E2399200 5 SWITCH, ROCKER 6 SENSOR, TEMPERATURE, STACK E2400300 7 GENERATOR, SPARK, IGNITOR, SOLID STATE E2338400 8 TUBING, SILICONE, 3/16" ID X 72" LONG Q0078821 Q0078821 9 ALUM.
Page 126 13.B Control Panel Assembly, Part Numbers 3 2 8 5 6 9 7 10 4 1 11 ITEM NO. 1 2 3 4 5 6 7* 8 9 10 11 ALL SIZES DESCRIPTION CONTROLLER ASSY, O2 SENSOR PANEL ASSY, CONTROL, SHEET METAL CABLE, DIAGNOSTIC HANDSET, 7 FT LONG CONTROLLER ASSY, Mfgr LINC® LABEL, CONTROL PANEL, MGT SWITCH, CUTOFF, LOW WATER LMV (Pre-Programmed and Model Serial # Specific) HANDSET, DISP & OPER, AZL23.00A9, SIEMENS TRANSFORMER ASSY, FLAME ROD POWER SUPPLY WITH JUMPER, AC/DC CONV.
Page 127 13.C B lower and Burner Assembly, Part Numbers. ALL Sizes Blower Gas-Air Mixer Part Numbers 1 2 3 3.0 4 * 5 2 1 3 2.0 4 * 5 1 2 1.0 & 1.5 3 4 * * = Blower Identified in High Voltage Box Parts Listing 5 Blower & Air-Gas Mixer, CFT 1.0 - 3.0 ITEM NO. 1 2 3 4 5 DESCRIPTION PART NO./BOILER SIZE 1.5 2.0 20N5095 V2028300 1.
Page 128 13.
Page 129 SINGLE PHASE 1Ø 9 9 10 10 12 5 11 2 1 208/240V 1Ø HX 1.0,1.5,2.0 120V 1Ø HX 1.0,1.5,2.0 THREE PHASE 3Ø 12 13 14 12 13 BOILER SIZE 10 11 10 11 ALL 208/480V 3Ø HX 2.0,3.0 1.0 - 1.5 2.0 2.0 3.0 ALL 600V 3Ø HX 2.0,3.
Page 130 13.E Burner Door Part Numbers Burner Door Part Numbers 1 2 7 6 5 1 3 9 8 4 3 11 10 DETAIL A SCALE 1 : 1.5 12 Burner Door Parts, CFT 1.0 - 3.0 ITEM NO. DESCRIPTION PART NO./BOILER SIZE 1.5 2.0 1.0 3.
INLET WATERWAY (Part of Boiler Weldment) 2 3 Outlet Waterway Part Numbers 5 Page 131 1 13.
8 3 13.H Gas Train Part Numbers GAS TRAIN PARTS, CFT 1.0 - 3.0 ITEM NO. DESCRIPTION PART NO./BOILER SIZE 1.5 2.0 3.0 V2025500 V2025600 V2025400 1.0 1 2 3 VALVE-ACTUATOR ASSY, GAS, VA SERIES, VKG ACTUATOR, ELECTRO-HYDRAULIC, SKP25.