Installation / Operation Instruction Manual

Table Of Contents
Page 84
CONFIGURATION
8.D.5.a Variable Speed Pump Control
The Variable Speed Pump Control Screen allows the adjustment of the following parameters:
On Delay – Upon a call for heat, once the unit ignites, this is the amount of time the unit will wait prior to
modulating the pump speed.
Proportional GainThis value is the corrective action that is proportional to the error (Set Point – Control
Temperature).
Integral Time – This value is applied to the sum of the error over a period of time.
Derivative Time – This value is applied
to the rate of change of the error.
Minimum SpeedThis is the minimum
speed to which the Vari-Prime will
control the pump.
Maximum SpeedThe is the
maximum speed to which the
Vari-Prime will control the pump.
O󰀨 Delay – Once the heat demand is
satised, Vari-Prime will control to the
maximum pump speed until the O󰀨
Delay time expires.
Delta T – Vari-Prime will control
the pump to maintain this delta T
(temperature rise) across the unit.
NOTE: VARI-PRIME
®
applies only to Boilers.
8.D.6 Manual Firing Rate
To navigate to the Manual Firing Rate Screen, touch the Manual Firing Rate Icon on the Conguration Screen.
The Manual Firing Rate Control Screen allows the adjustment of the following parameters:
Enable/Disable – Enables and disables the manual ring rate functionality.
Fan Speed – With the manual ring rate functionality enabled, an operator can manually set the ring rate. This
functionality is used for combustion adjustment purposes. With the manual ring rate functionality enabled, and the
desired fan speed set, apply a call for heat at CH1/DHW1 and the boiler will step through the ignition process and
run at the set fan speed.
Time Out – is the amount of time that the
operator has to adjust the Manual Firing
Rate before the control will go back to
automatic. It’s a walkaway timer and safety
feature.