8.D.2 DHW
(Domestic Hot Water)
To navigate to the DHW Screen, touch the DHW faucet icon on the Congure Screen.
DHW has all the same parameters as CH1 and CH2 with one exception. DHW has the following additional
parameters for adjustment:
DHW O󰀨set – Upon a DHW heat demand, the unit will control the outlet temperature to the DHW Set Point plus the
DHW O󰀨set (set point + DHW O󰀨set).
For example, with a DHW Set Point of 140°F and a DHW O󰀨set of 40°F, the unit will control the boiler outlet
temperature to 180°F (140°F + 40°F) to satisfy the heat demand.
NOTE: A DHW heat
demand can be initiated by
an aquastat or sensor, see
Section 7.E.3 on page 41