Installation / Operation Instruction Manual

Table Of Contents
Page 37
Figure 17. Condensation Trap Assembly
800.900.9276 Fax 800.559.1583 (Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867 603.335.6300 Fax 603.335.3355 (Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 905.238.0100 Fax 905.366.0130
www.Laars.com
Document 4378
Commercial FT, Condensate Trap Assembly Instructions
H2409900-
Page 1 of 1
1. The discharge hose 'end adapter'.
2. Hose adapter.
3. Hose clamps (3).
4. Transparent discharge hose.
5. The condensate trap (pre-assembled with cap &  oat).
6. Inlet Hose, 2.5" x .75".
7. Adapter, .75" barb x 1.0" NPT, PVC.
8. Mounting bracket (top half).
9. Mounting bracket (bottom half) with the velcro strap.
10. Screws (2).
NPT discharge
pipe on boiler
Kit Components
The mounting brackets overlap and are
fastened to the unit at existing holes.
Thread item 7 onto the discharge pipe at the
back of the unit. Do not over tighten.
Place the two mounting brackets together
and fasten them to the unit just below
the condensate discharge hose using
the 2 screws as shown.
Assemble items 1 thru 6 to make
the condensate trap sub-assembly.
There will be a remaining hose clamp.
Place it over the inlet hose and leave it loose.
With the 3rd hose clamp on the inlet hose, press the inlet side of the condensate trap assembly onto the PVC
adapter. The condensate trap will  t into the bracket as shown below. Tighten the third hose clamp su󰀩 ciently. Re-
check all hose clamps.
Use the velcro strap to fasten the condensate trap into the bracket assembly as shown below.
Run the Molex connector of the condensate trap sensor into the closest wiring grommet as shown. Reach into the
access panel and  nd the Molex connector on the inside (blue and blue/white wire) and connect them.
Attach the condensate disposal system of your choice to the 'end adapter'. Check for condensate leakage when
the unit is running.
6
7
8
10
9
To condensate
disposal system
The Completed View
5
4
2
3
1