Owner`s manual

29843-5-1012 Page 17
Example Of Possible Venting System Using One 90° Elbow
8 ft. (2.44 m) is listed as minimum vertical vent run with 20 ft.
(6.10m)ofmaximumhorizontalventrun.Verticaldimensionsare
basedoncenterlinetocenterlineofpipe.Horizontaldimensionsare
basedoncenterlineofpipetoexteriorofwall.
FIRESTOP AT
CEILING LEVEL
SEE GRAPH (Figure 21) FOR PERMISSIBLE
"H" AND "V" DIMENSIONS
Figure 24
Below Grade Installation
Whenitisnotpossibletomeettherequiredventterminalclearances
of12in.(305mm)abovegradelevel,asnorkelkitisrecommended.
Itallowsinstallationdepthdownto7in.(178mm)belowgradelevel.
The7in.(178mm)ismeasuredfromthecenterofthehorizontal
ventpipeasitpenetratesthroughthewall.
Ensure the sidewall venting clearances are observed. If venting
system is installed below ground, we recommend a window
well with adequate and proper drainage to be installed around
the termination area.
Typical Basement Installation
3” (76 mm) MINIMUM
18”
(457 mm)
MINIMUM
12”
(305 mm)
ABOVE
GRADE
48”
(121.9cm)
Figure 23
VENTING FIREPLACE