User's Manual
WASP™ NEST2 Smart Receiver and Gateway Operations Manual
- 25 -
3.2.9.10 Temperature Calibration
To set from the settings screen, scroll to, and select
TEMP CALIBRATION to calibrate the sensor
temperature reading to a reference reading. Using
the UP/DOWN and LEFT/RIGHT arrows enter the
reference reading from an external device such as
thermometer gun. Tap on OK to save the
calibration or tap on CANCEL to return to the
settings screen.
Example: If the WASP™ reads 23 °C and the
thermometer gun you are reading reads 26 °C, set the REF point to 26 °C for that sensor. This
automatically applies a preset multiplier to the sensor ensuring accuracy.
TEMP CALIBRATE (REF,'C)
21'C CRI=4 WRN=1 13:46 NOV 24/10
CANCEL
BACK
OK
REF C
025.2