46 | Making the electrical connections
Greenstar6 720 806 992 (2013/09)
7.2 Low voltage electrical connections in the Heatronic
boiler control
7.2.1 Open the Heatronic boiler control
Unhook the clip (step 1) and fold the Heatronic down (step 2).
Fig. 41 Fold the Heatronic down
Remove screws (step 1), unhook cable and remove cover (step 2).
Fig. 42 Remove the cover
7.2.2 Connecting the outdoor temperature sensor
Connecting the controls automatically establishes the internal
communications BUS connection ( see installation instructions for
the controls).
Punch out plastic insert.
Connect cable of the outdoor temperature sensor according to
Fig. 43.
Insert cable for the outdoor temperature sensor.
Secure the cable with the strain relief.
Fig. 43 Electrical wiring outdoor temperature sensor
7.2.3 Connecting the DHW tank temperature sensor (only heating
boiler ZBR..-3A)
Wire the DHW tank temperature sensor directly to the appliance
terminals. The sensor is provided with the appliance.
Do not exceed a sensor cable length of 33 feet (10 m).
Punch out plastic insert.
Plug connector into the circuit board.
Insert the cable of the DHW tank temperature sensor.
Secure the cable with the strain relief.
Fig. 44 Electrical connections DHW tank temperature sensor
NOTICE: Small pieces of wire can cause shorts and
damage the electronics.
Always strip cables away from electronics.
6 720 641 933-72.1O