Data Sheet

conjunction with an FACP that incorporates the
Cooper Notification sync protocol, a Cooper
Notification Sync Module, or the Cooper Notification
Power Supply. The Horn Appliances can be field set
for High (HI), Medium (MED), or Low (LO) dBA sound
output.
Strobe:
These strobes provide a non-synchronized strobe
appliance when connected directly to a Fire Alarm
Control Panel (FACP), or provide a synchronized
strobe appliance when used in conjunction with an
FACP that incorporates the Cooper Notification sync
protocol, a Cooper Notification Sync Module, or the
Cooper Notification Power Supply. They are designed
to flash at 1 flash per second minimum over their
Regulated Voltage Range.
Notice
Strobes are not designed to be used on coded
systems in which the applied voltage is cycled on
and off.
Compatible Products
The following Bosch Security Systems, Inc. products
are compatible with the Cooper Wheelock Exceder
Series Horn Strobes:
Category Product ID Product Description
Control Panels FPA-1000
1
Analog Addressable Fire
Panels
FPD-7024
1
Conventional or
Addressable
2
FACP
D10024A
3
Analog FACP
D8024
3
Analog FACP
D9124
3
Addressable FACP
D7024
3
Conventional or
Addressable
2
FACP
D7022
3
Conventional FACP
Modules SM‑12/24‑R Synchronization module
(red)
DSM‑12/24‑R Dual synchronization
module (red)
Power Supplies FPP-RNAC-8A-4C
1
Remote Notification
Appliance Circuit (RNAC)
Power Supply
PS‑24‑8MC
1
Power supply with built-in
synchronization protocol
1
These products have built‑in Cooper Notification
synch protocol.
2
When used with a D7039 Multiplex Expansion
Module, the FPD‑7024 and the D7024 become
addressable FACPs.
3
For synchronization, use the SM or DSM modules
with these control panels.
Mounting Considerations
The Universal Mounting Base supplied with each horn
strobe can be pre-wired. With the supplied Contact
Cover in place, the pre‑wired circuit can be checked
for continuity before the horn strobes are mounted.
The horn strobes snap onto the pre-installed Universal
Mounting Bases with the Contact Covers removed and
can be secured to the base with an optional securing
screw. The Universal Mounting Base flush mounts on
single-gang, double-gang, 4 in. square, 4 in. octal,
3.5 in. octal, and 100 mm European-type back boxes.
Wiring Considerations
The wiring terminals on the Universal Mounting Base
accept two appliance wires with diameters between
12 AWG and 18 AWG (ISO 4 mm
2
and 0.75 mm
2
) at
each terminal.
Parts included
Quant. Component
1 Horn Strobe appliance
1 Universal mounting base
1 Contact cover
1 Hardware pack
Two pan head mounting screws
One securing screw
1 Literature – Installation Instructions
Technical specifications
Electrical
Horn and Strobe Current Draw
4
24 V nominal (16.0 V to 33.0 V range)
Voltage
Type
Volume
Setting
Current Draw
DC: High: 15 cd: 82 mA, 30 cd: 102 mA,
60 cd: 141 mA, 75 cd: 148 mA,
95 cd: 176 mA, 115 cd: 197 mA,
150 cd: 242 mA, 177 cd: 282 mA
Medium: 15 cd: 73 mA, 30 cd: 87 mA,
60 cd: 128 mA, 75 cd: 139 mA,
95 cd: 163 mA, 115 cd: 186 mA,
150 cd: 230 mA, 177 cd: 272 mA
Low: 15 cd: 65 mA, 30 cd: 84 mA,
60 cd: 120 mA, 75 cd: 136 mA,
95 cd: 157 mA, 115 cd: 184 mA,
150 cd: 226 mA, 177 cd: 267 mA
FWR: High: 15 cd: 131 mA, 30 cd: 138 mA,
60 cd: 220 mA, 75 cd: 216 mA,
95 cd: 258 mA, 115 cd: 289 mA,
150 cd: 357 mA, 177 cd: 384 mA
Medium: 15 cd: 112 mA, 30 cd: 126 mA,
60 cd: 202 mA, 75 cd: 201 mA,
95 cd: 247 mA, 115 cd: 272 mA,
150 cd: 340 mA, 177 cd: 378 mA
2 | W‑HSxC Ceiling‑mount Multi‑candela Horn Strobes