3. From the AutoDome main menu, select Alarms Setup>Inputs Setup, and set the Alarm
Input # to N.O.S. See the table below for contact and condition details.
6.2.2 Configuring a Normally Closed Supervised Alarm
1. Install a 2.2 K end-of-line resistor in the alarm circuit.
2. Connect the alarm wires to input 1 or 2 (pin 5 or 6) and to the ground (pin 7) at the
AutoDome.
Figure 6.2 N.C.S. - Normally Closed Supervised Connections
3. From the AutoDome main menu select Alarm Setup>Inputs Setup, and set Alarm Input #
to N.C.S. See the table below for contact and condition details.
6.3 Configuring Non-supervised Alarms (inputs 1 through 7)
You can configure alarms 3 through 7 as non-supervised Normally Open (N.O.) or Normally
Closed (N.C.) alarms.
AutoDome Programmed N.O.S.
Contact Alarm Condition
Open Normal
Closed Alarm
Cut or brake Tamper
1 Dry Contact 3 Dome Connector
2 Alarm 1 or 2 only (Pin 5 or 6) 4 Ground (Pin 7)
AutoDome Programmed N.C.S.
Contact Alarm Condition
Open Alarm
Closed Normal
Short Tamper
2.2K