Technical data

Minimum current 10 mA (per contact)
Maximum current load 1,000 mA (per contact)
Utilization category DC-13 (according to IEC 60947-5-1)
Fig.4-3: Technical data of the STOP push button
4.4 Enabling Device
Nominal voltage:
24 V DC (voltage tolerance 19.2 V DC to 30 V DC according to EN 61131-2)
Nominal current:
1)
max. 500 mA
Prescribed external fusing 2 A time-lag safety fuse
Operating cycles
switch position 2: 10
5
switch position 3: 5 x 10
4
output type solid state output
Maximum breaking current circuit 1: 1.5 A
circuit 2: 0.8 A
Maximum inductive load circuit 1: 145 mJ / 1.16 H at 24 VDC, 500 mA (comparable with DC13 according
to EN 60947-5-1)
circuit 2: 145 mJ / 1.16 H at 24 VDC, 500 mA (comparable with DC13 according
to EN 60947-5-1)
Short circuit and overload protection circuit 1: yes (integrated in the output-FET)
circuit 2: yes (through protective circuit)
Reverse voltage protection circuit 1: yes
circuit 2: yes
Actuation forces from switch 1 to 2: typically 5N
from switch 2 to 3: typically 10 N
Fig.4-4: Technical data of the enabling device
4.5 Connection Module VAC 30.2
Connections 1 x ethernet connection (RJ 45, 10/100 Base-T)
STOP push button
Enabling device
Power supply 24 V (see IndraControl VCH 08.1)
Prescribed external fusing 2 A time lag safety fuse
Material front panel: aluminum, metal cover: V2A
Degree of protection front panel IP 65, rear side IP 30
Fig.4-5: Technical data of the IndraControl VAC 30.2
1)
Please
fuse cables against short circuits and cross circuits caused by the installation!
18/80 Bosch Rexroth AG | Electric Drives
and Controls
Rexroth IndraControl VCH 08.1 | Project Planning Manual
Technical Data