Data Sheet
For 24 V applications, the total number of strobes on a
single NAC must not exceed 40, with a maximum loop
resistance of 120 Ω. For 12 V applications, the total
number of strobes must not exceed 12, with a
maximum loop resistance of 30 Ω.
Certifications and approvals
System Sensor holds these Listings and Approvals:
Region Certification
USA UL ULSZ: Audible Signal Appliances
(UL464)
FM SS-P Family
CSFM see our website
Installation/configuration notes
Mounting Considerations
These horn strobes mount on a standard 4‑inch square
back box, a 4‑inch octagon back box, a single‑gang
back box, or a double‑gang back box.
Wiring Considerations
The input terminals on the universal mounting plate
accept solid wires between 12 AWG (2.3 mm) to
18 AWG (1.2 mm).
Parts included
Quant. Component
1 Horn strobe
1 Universal mounting plate (MP120K)
1 Hardware pack
1 Literature pack
Technical specifications
Electrical
Current Draw, UL maximum at 8 V to 17.5 V
Standard-candela Models only
15 cd - Temporal Code 3 Pattern
DC FWR
High dB Setting: 137 mA 136 mA RMS
Medium dB Setting: 132 mA 129 mA RMS
Low dB Setting: 132 mA 129 mA RMS
15 cd – Non‑temporal (continuous) Pattern
DC FWR
High dB Setting: 141 mA 142 mA RMS
Medium dB Setting: 133 mA 134 mA RMS
Low dB Setting: 131 mA 132 mA RMS
15/75 cd - Temporal Code 3 Pattern
DC FWR
High dB Setting: 147 mA 155 mA RMS
Medium dB Setting: 144 mA 152 mA RMS
Low dB Setting: 143 mA 151 mA RMS
15/75 cd – Non‑temporal (continuous) Pattern
DC FWR
High dB Setting: 152 mA 161 mA RMS
Medium dB Setting: 145 mA 155 mA RMS
Low dB Setting: 144 mA 154 mA RMS
Current Draw, UL maximum at 16 V to 33 V
Standard-candela Models
15 cd - Temporal Code 3 Pattern
DC FWR
High dB Setting: 79 mA 88 mA RMS
Medium dB Setting: 69 mA 78 mA RMS
Low dB Setting: 66 mA 76 mA RMS
15 cd – Non‑temporal (continuous) Pattern
DC FWR
High dB Setting: 91 mA 103 mA RMS
Medium dB Setting: 75 mA 85 mA RMS
Low dB Setting: 68 mA 80 mA RMS
15/75 cd - Temporal Code 3 Pattern
DC FWR
High dB Setting: 90 mA 97 mA RMS
Medium dB Setting: 80 mA 88 mA RMS
Low dB Setting: 77 mA 86 mA RMS
15/75 cd – Non‑temporal (continuous) Pattern
DC FWR
High dB Setting: 100 mA 112 mA RMS
Medium dB Setting: 85 mA 95 mA RMS
Low dB Setting: 79 mA 90 mA RMS
30 cd - Temporal Code 3 Pattern
DC FWR
High dB Setting: 107 mA 112 mA RMS
Medium dB Setting: 97 mA 103 mA RMS
Low dB Setting: 93 mA 101 mA RMS
30 cd – Non‑temporal (continuous) Pattern
2 | SS‑P Two‑wire Indoor Horn Strobes