Installation manual
Solution 64
2
Bosch Security Systems | 12/05 | FTR1.1
9)
NEW
Auto Arm Time Extended Report
If the user extends the auto arm time, the panel will report a CID
event 464 to the monitoring station.
10)
NEW
EOL Resistor Value Changes
The following EOL resistor values have been added making it
easier to change over of Tecom and Concept panels.
Type 11 = 6K8 with Tamper (2K2)
Type 12 = 10K with Tamper (10K)
To allow for these two options we have removed support for 12K
and 15K EOL resistor values.
Inputs > Global Input Options >
EOL Value
MENU 3-4-0
0 = No EOL 5
1 = 1K0 6 = 4K7 11 = 6K8 with Tamper (2K2)
2 = 1K5 7 = 5K6 12 = 10K with Tamper (10K)
3 = 2K2 8 = 6K8 13 = 22K
4 = 2K7 9 = 8K1 14 = 3K3 with Tamper (6K8)
5 = 3K3 10 = 10K 15 = Split EOL (Parallel)
(3K3 = Primary, 6K8 = Secondary)
11)
NEW
View Status in Part Mode
This feature allows the end user to view detailed system status
information while the system is armed in Part mode. Press the
down arrow to obtain a status list showing any system troubles
currently in eect as well as zone and output status information.
12)
NEW
Keypad and Keyfob Alarm Display
Emergency alarms such as Keypad Fire, Medical and Panic alarms
and Keyfob Panic alarms will now display in the status scroll list
as well as in the drop down list.
The status message will show the alarm type and keypad
number which the alarm was generated from and in the case of
a keyfob panic alarm the user name and number will be shown.
13)
NEW
PGM Input - Exit Timer
Version 1.04 now forces the exit timer to run when the panel
has been armed via the programmable input. For example if
the input is programmed for Pulse On/O and a trigger signal is
received then the exit timer will begin and the system will not
fully arm until the exit time expires.
14)
NEW
PGM Input to Arm All Areas
New in V1.04 When the Programmable Input is congured as
an on/o input, a valid trigger signal will cause all areas on the
panel to arm and or disarm. If you require individual area arm /
disarm control you should use a key-switch zone.
Earlier versions would only arm Area 1.
15)
NEW
Strobe Pulse Time Extended
The strobe pulse ash duration for On / O indication has been
extended to 5 seconds for OFF and 10 seconds for On. These
times are xed and should allow for most strobe types in the
market today
16)
NEW
Direct Link Request Command
Comms > Commands >
Start Direct Link
MENU 5-0-5
This command performs the same function as holding down the
default switch on the Vision panel for 5 seconds. Once initiated,
the panel will enter direct link mode ready to communicate with
the Solution Link software. The green status LED on the panel
will ash slowly indicating the function has been activated.
17)
NEW
Real-Time Program Update During Downloads
Version 1.04 includes a new function which will update EOL
resistor value changes and zone state changes in real time.
Changes are updated every time a download is performed
during the Solution Link session.
18)
NEW
Daylight Savings Option Change
Version 1.04 includes a change to the week of the month
parameter used in the Summer Time on and Summer Time O
options. Week 5 has been replaced with Last week. Daylight
savings time changes take eect on the last Sunday of the
month in Europe.
19)
NEW
”Block If All On” Output Option
Version 1.04 includes a new output option called Block If All On.
Outputs > Properties >
Output Options
MENU 4-1-5
1 Do Not Operate On Low Battery Y
2 Display Overload Y
3 Report Overload Y
4 Display Device Fail Y
5 Report Device Fail Y
6 Alarm On Device Fail N
7 Block If All On N
8 Display Status Message N
Selecting this option will prevent the output from operating if
the panel is armed in the all on mode. This option is particularly
useful when using a radio keyfob for arm and disarm as well as
garage door control.
Enabling the Block If All On option on the output which
is controlling the garage door will prevent the user from
accidentally opening the door before they disarm the system.