Specifications

Electrical | 9SM CS Series Heat
8 733 920 846 (2014/01)Revised 01-14
INTELLIGENT RESET: If a fault condition is
initiated, the 5 minute delay on break time period is
initiated and the unit will restart after these delays
expire. During this period the fault LED will indicate
the cause of the fault. If the fault condition still
exists or occurs 2 or 4 times (depending on 2 or 4
setting for Lockout dip switch) before 60 minutes,
the unit will go into a hard lockout and requires a
manual lockout reset. A single condensate overflow
fault will cause the unit to go into a hard lockout
immediately, and will require a manual lockout
reset.
LOCKOUT RESET: A hard lockout can be reset
by turning the unit thermostat off and then
back on when the “RESET” dip switch is set to
“Y” or by shutting off unit power at the circuit
breaker when the “RESET” dip switch is set to
“R”.
The blower motor will remain active during a
lockout condition.