Specifications
Canada wiring – auxiliary terminal block and connections
Fitting the auxiliary terminal block (see diagram below).
RP17PT RP27PT
• Connect the red wires from the left hand terminal of the new block to the L1 terminals in the unit.
(There are two red wires required in the RP17PT and three in the RP27PT).
• Connect the blue wires from the right hand terminal of the new block to the L2 terminals in the unit.
(There are two blue wires required in the RP17PT and three in the RP27PT).
• Push and click the auxiliary terminal block onto the louvered rail in the backplate.
Connecting the supply cable - Canada only - not for the USA.
• The RP17PT requires an 80A 240V AC
single phase supply protected by an 80A
double pole circuit breaker.
• The RP27PT requires a 120A 240V AC
single phase supply protected by a 120A
double pole circuit breaker.
• The power cable size and the installation must be in accordance with the Canadian Electrical Code,
C22.1-02.
• The incoming hole diameter on auxiliary terminal block can accept up to 1/0 AWG size cables.
• The cable entry is via the 1 ¼ inch cable entry hole on the bottom right hand edge of the backplate.
• Strip back the insulation on the power wires about ½ inch. Connect the ungrounded conductors to
the terminals “L1” and “L2” on the auxiliary terminal block.
• Any insulation on the ground wire should be stripped back about ¾ inch. The ground lead must be
connected to the pillar terminal marked “GR.”
• Make sure the terminal block screws are tightened securely. Loose connections can cause wires to
heat up.
• Make sure that the ground wire is wrapped around its terminal stud and into the saddle washer. The
nut should be tightened securely.
• Attach the front cover and tighten the retaining screws.