Technical data

R911305038 / 01 | Rexroth VCP-Operating Concept Electric Drives and Controls | Bosch Rexroth AG 5-67
Standard Mode
RepoutRepText41P
RepoutRepText61P
RepoutSelectGroupP
Function Displays the most recent parallel message beginning from the 41st
character. The message is displayed in accordance with the speci-
fied representation settings.
Data type Alphanumeric
Representation
type
Alphanumeric
Configurable val-
ues
Function Displays the most recent parallel message beginning from the 61st
character. The message is displayed in accordance with the speci-
fied representation settings.
Data type Alphanumeric
Representation
type
Alphanumeric
Configurable val-
ues
Function Sets the group numbers whose messages are displayed.
Data type Numeric
Representation
type
Positive decimal number, alphanumeric, selection text, selection im-
age, hexadecimal number, binary number
Configurable val-
ues
0 to
256
Each group is represented by one bit of a byte. A logical '1' in bit 0 acti-
vates group1, in bit 1 activates group2 and so on.
The settings for a message field override the settings for this system
variable! To prevent the settings in the operating device from being
overridden, you must activate the Global Settings function for the mes-
sage field.