Technical data

R911305038 / 01 | Rexroth VCP-Operating Concept Electric Drives and Controls | Bosch Rexroth AG 5-27
Standard Mode
Just below, enter the height for the recipe field in the mask
The Font area specifies the character set used to display all elements
of a recipe field on the operating device. To display all elements of a
recipe field in another font, click the New Font button.
Table Field
The Table field classifies the area in a mask used to display values in a
table.
Select the Table Field icon in the toolbar and in the mask select the
area where the table will be displayed. This area is displayed as a rect-
angle. The table field is marked with the letter T on the left edge of the
rectangle. You can use the sizing handles to change the height of the
area. You cannot change the width of the area.
Specify here, how many lines the table field will have and how many
elements can be displayed in this table field.
The Font area specifies the character set used to display all elements
of the table on the operating device. To display all elements of a table
in another font, click the New button.
To display variable values in the table, create a variable frame in the
table field. Specify the address for the variable and select the represen-
tation type.
Variables displayed in a button that has a frame cannot be dragged
with the mouse to the table field. Frames of buttons cannot be dis-
played in tables.
Example: You have 256 elements you want to be displayed in a table which has
four columns. The operating device has screen with 20 lines.16 of
these lines are to be used to display elements. Therefore, create a
table field with a height of 16. Enter 64 (16 lines x 4 elements) for the
number of table elements.
5.5.4 Field Type
By selecting a field type, you determine whether the operator will be
able to modify the variable's value or whether the value is just dis-
played.
For password entry, you can specify the field type in more detail.
5.5.4.1 Input
Select the field type Input to enable operators to change the value of a
variable on the operating device.