6-118 Bosch Rexroth AG | Electric Drives and Controls Rexroth VCP-Operating Concept | R911305038 / 01
INTERBUS MMICOM raw
By setting up the following system variables in one of the masks in the
projects, you can log the error messages with the operating device.
– ComParityCount to log the number of the error codes 59.
– ComOverrunCount to log the number of the error codes 60.
– ComFrameCount to log the number of all other error codes.
58 Access error. The subcode indicates the vari-
able number - in decimal format - which was
being edited when the error occurred.
No valid data cycles are
executed on the INTER-
BUS.
59 Wrong variable number received. The subcode
indicates the variable number - in decimal format
- which was being edited when the error occur-
red.
The 8 byte user data are
not consistent. There is an
error within the controller
board.
60 Wrong PD index received. The subcode speci-
fies the received PD Index in decimal format.
The 8 byte user data are
not consistent. There is an
error within the controller
board.
Code Subcode Error Type Possible Cause
Fig. 6-177: Error Messages - MMICOM