Technical data

6-118 Bosch Rexroth AG | Electric Drives and Controls Rexroth VCP-Operating Concept | R911305038 / 01
INTERBUS MMICOM raw
By setting up the following system variables in one of the masks in the
projects, you can log the error messages with the operating device.
ComParityCount to log the number of the error codes 59.
ComOverrunCount to log the number of the error codes 60.
ComFrameCount to log the number of all other error codes.
58 Access error. The subcode indicates the vari-
able number - in decimal format - which was
being edited when the error occurred.
No valid data cycles are
executed on the INTER-
BUS.
59 Wrong variable number received. The subcode
indicates the variable number - in decimal format
- which was being edited when the error occur-
red.
The 8 byte user data are
not consistent. There is an
error within the controller
board.
60 Wrong PD index received. The subcode speci-
fies the received PD Index in decimal format.
The 8 byte user data are
not consistent. There is an
error within the controller
board.
Code Subcode Error Type Possible Cause
Fig. 6-177: Error Messages - MMICOM