Technical data
R911305038 / 01 | Rexroth VCP-Operating Concept Electric Drives and Controls | Bosch Rexroth AG 6-87
DeviceNet
6.6.6 EDS File
The EDS file ensures that the Poll I/O Connection is automatically
installed between the DeviceNet master and operating device.
6.6.7 Physical Interfacing
Plug-in connectors on the operating device for connection to the
DeviceNet bus.
For the connection to the bus, use twisted pair, shielded cables only.
Terminate both ends of the bus with terminating resistors.
All signal lines in the operating device are bridged from X2.1 to X2.2.
Connect the connecting cables to all pins, including the reserved pins.
This allows continued use of the cables, even if the bus specification is
extended in the future.
0x8A
(Memory
Object)
0x33 (Read) 0x01 0x01 Service
Data
Block String Read
0x35 (Write) 0x01 0x01 Service
Data
Block String Write
Class ID
(1 Byte)
Service ID
(1 Byte)
Instance ID
(1 Byte)
Service Data Service Name
Attribute ID
(1 Byte)
Data (n
Byte)
Fig. 6-138: Format of the Explicit Message
Pin Designation Function
1 nc Not Connected
2 CAN_L CAN_L Bus Line (Dominant LOW)
3 CAN_GND CAN Ground
4 nc Not Connected
5 nc Not Connected
6 CAN_GND CAN Ground
7 CAN_H CAN_H Bus Line (Dominant HIGH)
8 nc Not Connected
9 nc Not Connected
Fig. 6-139: Pin assignment X2.1 / X2.2 CAN bus