Technical data
6-78 Bosch Rexroth AG | Electric Drives and Controls Rexroth VCP-Operating Concept | R911305038 / 01
DeviceNet
6.6.3.4 System Variables
Since the operating devices do not have diagnostic LEDs, you need to
use system variables to indicate specific DeviceNet statuses. You can
create these system variables within any mask as output variables. To
do so, select the representation type Selection Text and link the vari-
able with a text list containing a text string for each status.
ComBaudrateA
This system variable can be used to indicate the statuses of the
module/network LED.
ComHandshakeA
This system variable allows you to indicate whether the data memory
has been initialized by the master.
Value Text Meaning
0LED Off
1 LED Green Device is assigned
2 LED flashes green DUP_MAC_ID test is OK
but a connection has not
been established
3 LED Flashes Red Connection terminated af-
ter a time delay
4 LED Red BUS-OFF status
5 LED flashes red and green DUP_MAC_ID error
Fig. 6-118: Statuses of the module/network LED
See chapter „Byte 1 - Initialization“ on page 6-73.
Value Status
0 Not initialized
1 Initialized
Fig. 6-119: Initialization states of the data memory