Technical data

6-72 Bosch Rexroth AG | Electric Drives and Controls Rexroth VCP-Operating Concept | R911305038 / 01
DeviceNet
The byte order for the
word address,
number of bytes and
data word
can be specified in the communication parameters.
6.6.1.6 Fragmentation
By means of fragmentation, up to 384 bytes can be transferred in one
explicit message.
6.6.2 Poll I/O Connection
The Poll I/O Connection can be used for event-controlled exchange of
data between the master and the slave.
On account of the EDS data, the Poll I/O Connection is installed auto-
matically between the DeviceNet master and the operating device.
With this connection, 2 bytes are transferred cyclically from the control-
ler’s OUT area to the operating device and 5 bytes are transferred from
the operating device to the IN area of the controller.
6.6.2.1 Receive Data of the Operating Device (Consumed Data)
The Consumed Connection Size is 2 bytes.
See chapter „Byte Order“ on page 6-76.
Byte Designation
1 Initialization
2 Control Byte
Fig. 6-108: Structure of the Consumed Data