Technical data

R911305038 / 01 | Rexroth VCP-Operating Concept Electric Drives and Controls | Bosch Rexroth AG 6-57
Bosch BUEP19E
6.5 Bosch BUEP19E
The Bosch BUEP19E protocol allows you:
random read and write access to all PLC data
bit-by-bit access to all byte, word and double-word oriented data ty-
pes
byte-by-byte access to all data words in a data block.
The size of the address area depends on the controller being used.
This protocol supports a connection to the following CPU modules:
CL200
CL350
CL400
CL500
6.5.1 Data Types
Direct access is possible to the following data types.
The size of the individual data areas depends on the controller of the
controller's CPU.
Type Mnemonic Access
Input Bit BE Bit Access
Input Byte BYE Byte Access
Input Word WE Word Access
Input Double-Word DWE Word Access
Output Bit BA Bit Access
Output Byte BYA Byte Access
Output Word WA Word Access
Output Double-Word DWA Word Access
Flag Bit BM Bit Access
Flag Byte BYM Byte Access
Flag Word WM Word Access
Flag Double-Word DWM Word Access
Timer Word WT Word Access
0 to 127
Counter Word WZ Word Access
0 to 127
Fig. 6-89: Data types for Bosch BUEP19E