6.4.4 Error Messages
Error messages are displayed on the operating device along with a
code and subcode. Error messages are composed as follows.
Communication Error
Code XXXXX
Subcode XXXXX
Retries XXXXX
Code Subcode Error Type Possible Cause
1 Slave not ready Wrong baud rate or cable
defective
2 Packets out of sequence
3 Error in protocol frame
4 Waiting time elapsed (Timeout) Connection interrupted.
6 Wrong parity
7 Send process aborted
8 Receive process aborted
9 Cyclic buffer overrun Cyclic buffer too small
10 No cyclic data defined
12 Cyclic data already defined
15 Protocol error The selected protocol is not
supported.
16 Receive buffer overrun
40 System variable error Undefined system variable
Bosch-Specific Error Messages
50 No connection set-up
51 Wrong acknowledgement during connection set-
up
52 Wrong acknowledgement after sending informa-
tion block
53 No response telegram
54 Timeout - No response telegram
55 Block time exceeded
56 No acknowledgement
57 EOT - Aborted by controller
Fig. 6-88: Error Messages for Bosch BUEP19