Technical data

5-166 Bosch Rexroth AG | Electric Drives and Controls Rexroth VCP-Operating Concept | R911305038 / 01
Standard Mode
•Date
•Time
Message text with up to 255 characters
The values of up to two variables, from the time the message ap-
pears (only if available)
When a new project is being created, existing messages can be trans-
ferred individually or completely.
Message Number
For external messages, the message number also determines the pri-
ority of the message. The message with the number 1 has the highest
priority, and the message with the number 9999 has the lowest priority.
You do not have to assign continuous message numbers.
The assignment of the message numbers in the area for status mes-
sages always starts with 1.
From the system, you can also use status message texts in the serial
message system.
Message Text and Variable
The text length must not exceed 255 characters, including a formatted
variable. The programming system will not allow you to enter texts
longer than this.
The standard size of all characters of the operating device specified in
each case is permitted. Each message text can contain two output vari-
ables.
The output format of the variables is identical to the one-off output vari-
ables in input/output masks. In this way, for example, coded texts can
be used to modify individual messages or to use them for several sta-
tuses.
The output format of the message line can be changed online in a con-
figuration mask for the message mask.
Make sure that the serial and parallel message systems do not overlap!
If you want both message systems to be independent of each other,
make sure that the message numbers of the serial system start above
the status messages.
f you would like to program full-page message outputs, you must har-
monize the message and mask numbers.
See chapter “Full-Page Message Output“ on page 5-172.