Technical data

5-148 Bosch Rexroth AG | Electric Drives and Controls Rexroth VCP-Operating Concept | R911305038 / 01
Standard Mode
Using the Size of Message Buffer, you define how many messages can
be stored in the operating device. Specify the maximum number of
messages to be managed by the operating device.
You can have the messages displayed in indented format. To do so,
specify the number of characters by which the lines are to be indented
after the first line. The value you enter here refers only to the display of
messages in the operating device's message field.
The same options are available for outputting messages to the logging
printer.
You can choose from four variants for outputting to the printer.
1. Print the entire message, SER2 reserved exclusively for message
output
2. Formatted printout, SER2 reserved exclusively for message output
3. Print the complete message, SER2 reserved only temporarily for
message output
4. Formatted printout, SER2 reserved only temporarily for message
output
Serial Message System From the controller, you can erase all acknowledged messages if
you write the bit pattern E216h to the controller address Delete Mes-
sages and write the control code 7FF5h to the serial message chan-
nel.
If you want to delete all messages, you need to write the control code
7FFEh to the serial message channel. If you want to use this function
of the operating device, you must assign a variable for deleting mes-
sages.
Parallel Message System For the parallel message system, you must enter a Variable for Status
Messages as the start address of the data area where the messages
are stored in the controller in bit-coded form.
You can also specify a name for a Variable for Acknowledging Status
Messages of the same size.
You also define the number of bytes to define the Size in Bytes of the
area for the status messages in the controller.
You can define a maximum of 256 bytes for this area.
By entering the polling time, you also specify the interval at which the
operating device reads the data area of the status messages from the
controller.
For the polling time, you can enter values from 0 to 25.5 seconds.
The active messages are displayed in an I/O screen with a message
field for parallel messages. The status messages can be sorted