Standard Mode
5.6 Dynamic Attributes
For the mask elements Static Text, Text Field, and Variable, you can
assign 255 ranges of values for dynamic attributes.
Dynamic attributes change the display of a text or variable value in the
operating device, based on a variable or control variable value.
The system displays the values for the upper and lower limit in a list
box. In the same line, it displays the attributes for values that are within
the limits. You cannot enter overlapping value ranges!
1. Enter the values for the upper and lower limit under the list box.
2. Select the corresponding attributes in the relevant check boxes.
3. Assign the attributes to the range of values. The range of values and
its attributes are simultaneously entered in the list box.
The dynamic attributes are either derived directly from the value of a
variable or from the value of a corresponding control variable.
For variables in input and output masks, the entry of a control variable
is optional.
In general, no control variables are permitted in recipes. Here, the
dynamic attributes can only be derived from the value of the variables.
For texts in input/output masks, a control variable is always required to
control the attributes.
You cannot assign dynamic attributes for texts in recipes.
To assign dynamic attributes, carry out the following steps:
1. Click one of the lines in the list box.
2. Enter limit values into the appropriate fields.
3. Select the corresponding attributes.
4. Enter the name of the control variable, if needed.
5. Click the Assign button.
You can assign the following attributes:
Underline
•Inverse
•Flashing
Invisible
Non-editable
Foreground
Background
You can display up to 25 objects with dynamic attributes in a mask.