PRODUCT INFORMATION PI--34.65d MAGIC.SENS This product information includes the entire MAGIC.SENS -- product range. Page 1 of 42 BDL--4998121218 A23.en / 09.02.
Product Information MAGIC.SENS -- Product range PI -- 34.65d Table of Contents 1. Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2. 2.1. 2.2. 2.3. Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration of the Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Functional Description of Sensor Technology . . . . . . . . . . . . . . . . . . . System Description MAGIC.SENS . . . LSN . . . . . . . . .
Product Information MAGIC.SENS -- Product range 7. PI -- 34.65d 7.1. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Support Plates for Detector Zone Identification . . . . . . . . . . . . . . . . . 25 7.1.1. 7.1.2. 7.1.3. Support Plate TP4 400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Support Plate TP8 400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Product Information MAGIC.SENS -- Product range 1. PI -- 34.65d Foreword The MAGIC .SENS fire detector series combines standard detection procedures such as scattered light measurement and temperature measurement in their highest stage of expansion with gas measurement technology. Here, the signals of scattered light sensors, temperature sensors, and gas sensors are processed with the help of modern signal--processing procedures.
Product Information MAGIC.SENS -- Product range 2. PI -- 34.65d Product Description 2.1. Configuration of the Detector 1 = Smoke measuring chamber (Optical sensor) 2 = Thermal sensor 3 = Chemical sensor (covered on the cross--section) 3 4 2 1 4 = Individual display 5 = PC board with evaluation electronics 5 6 = Base MS 400 6 2.2. Functional Description of Sensor Technology 2.2.1. Optical sensor (smoke detector) The optical sensor works according to the scattered light method.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 2.3. System Description MAGIC.SENS . . . LSN Up to three detection principles are integrated into the multisensor detector MAGIC.SENS . . . 400/410 LSN: 1. Optical (for smoke) 2. Thermal (for heat) OTC, OC, OT, O, T 3. Chemical (for gas) The individual sensors can be programmed via the LSN network manually or time--controlled. All sensor signals are evaluated continually by the internal signal analysis electronics and are linked with each other.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 2.4. System Description MAGIC.SENS . . . GLT Up to two of the following detection principles are integrated into the multisensor detector MAGIC.SENS . . . 300/310 GLT: 1. Optical (for smoke) 2. Thermal (for heat) 3. Chemical (for gas) OC, OT, O, T All sensor signals are evaluated continually by the internal signal analysis electronics and are linked with each other.
Product Information MAGIC.SENS -- Product range 3. PI -- 34.65d Planning Notes MAGIC.SENS fire detectors are not intended for external use! 3.1. Basic Planning Specifications D The planning of multisensor fire detectors (combination detectors) occurs according to the guidelines for optical detectors until an independent guideline has been worked out with the VdS.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 3.4. Use in Explosive Areas All MAGIC.SENS detector types conform to the device category 3G, gas group IIB, and temperature class T6, in accordance with the European guideline 94/9/EG (ATEX). Thus the detectors may be used in Zone 2 areas where there is danger of explosion! Limiting values: D Detectors may only be operated with central units whose line output is energy--limited according to EN 50021. . This is a given for all Bosch fire panels.
Product Information MAGIC.SENS -- Product range 4. PI -- 34.65d Programming Programming is setting a LSN detector to the desired operating mode. Programming is carried out with the >WinPara< software using a PC or laptop connected to the fire panel. All sensor signals are analyzed continually by the internal evaluation electronics and are linked with each other via an inbuilt microprocessor. The detectors OTC 410 LSN OC 410 LSN and OT 400 E LSN are programmed by specifying the operation location (e.g.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 4.1. MAGIC.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 4.3. MAGIC.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 4.5. MAGIC.SENS T 400 E LSN Selectable sensitivity classes in the >WinPara< programming software § A2R Typical application temperature: 25_C, Tmax + Tdiff, height up to 6m A2S Typical application temperature: 25_C, only Tmax, height up to 6m A1R Typical application temperature: 25_C, Tmax + Tdiff, height 6--7.5m A1 Typical application temperature: 25_C, only Tmax., height 6--7.5m BR Typical application temperature: 40_C, Tmax + Tdiff.
Product Information MAGIC.SENS -- Product range 5. PI -- 34.65d Technical Data MAGIC.SENS 5.1.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 5.2. Technical Data: O 400 E LSN / T 400 E LSN Detector type O 400 E LSN T 400 E LSN Detection principle Scattered light measurement Measurement of absolute temperature and temperature increase Special features Contamination detection Drift compensation in optical unit Operating voltage 15 V DC . . . 33 V DC Current consumption < 0.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 5.3.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 5.4. Technical data: T 300 GLT / T 300 FSA GLT Detector type T 300 T 300 / FSA Detection principle Measurement of absolute temperature and temperature increase Measurement of absolute temperature and temperature increase Special features Goods monitoring for fire barriers according to DIBt. Characteristic curve according to class A1R according to EN 54--5 Class A2R according to EN 54--5 Operating voltage 12 V DC . . .
Product Information MAGIC.SENS -- Product range PI -- 34.65d 5.5. Country approvals Country Germany y (D) Approval institution VdS Schadenverhütung GmbH DIBt German Institute for Building Technology Belgium g (B) Bulgaria ( BG ) PTB Physical.
Product Information MAGIC.SENS -- Product range PI -- 34.65d Country approvals (continued) Country Hong g Kong g ((HK)) Israel ( IL ) Croatia ( HR ) Lithuania ( LT ) Approval institution Detector type Approval no.
Product Information MAGIC.SENS -- Product range PI -- 34.
Product Information MAGIC.SENS -- Product range 6. PI -- 34.65d Detector base 6.1. Detector base MS 400 The MAGIC SENS detector module is placed in the MS 400 detector base, which is used for both concealed and surface cable insertion. The detector base is made of white ABS plastic (Novodur, color similar to RAL 9010) and it has a matte surface. The base has 7 screw terminals for the connection of the detector and its accessories to the fire panel.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 6.1.2. Connection of the detector base MS 400 (surface cable insertion) Cable insertion and feed--out possible on the same side wh = white ye = yellow bl = black rd = red bl ye ye rd wh white yellow C red black For GLT (conventional technology): EOL = end of line resistor (End of line module) a1/a2 LSN -- / L..a (GLT) b1,b2 LSN + / L..b (GLT) +V 0V indicator output (see table p.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 6.2. Detector Base with Damp Room Seal MSF 400 For use of the detector in a humid environment, there is the MSF 400 detector base. The MSF 400 detector base with integrated seal of TPE protects the detector reliably against the penetration of condensed water. Concealed and surface cable insertion possible. 6.3.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 6.4. Detector Base Sirens MSS 300 / 400 / 401 If directly at the location of the fire the acoustic signaling of an alarm is required, the detector base sirens, available in 8 variants, are used. -- Detector base siren MSS 300 in white and red, for the conventional line technology and connection via the C--point of the detector. -- Detector base siren MSS 300 WS--EC in white, for the conventional line technology with external activation.
Product Information MAGIC.SENS -- Product range 7. PI -- 34.65d Accessories 7.1. Support Plates for Detector Zones Identification The support plates are made of 1.8mm thick ABS -- plastic (Novodur, color similar to RAL 9010) and are clamped between the detector base and the ceiling. 7.1.1. Support plate TP4 400 The support plate TP4 400 is intended for an installation height up to 4m and is designed for labels up to a size of approximately 65 x 34 mm. 7.1.2.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 7.2. Basket Guard SK 400 The basket guard SK 400 is installed over the detector and protects the detector against damage to the greatest possible extent. If the detector is mounted in a sports facility, for example, the basket guard prevents balls or other sports equipment from hitting the detector and damaging it. 7.3.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 7.6. MPA External Detector Alarm Display The MPA external detector alarm display is required if the detector is not directly visible or has been mounted in false ceilings/ or floors. The MPA should be mounted in corridors or access pathways to the corresponding building sections or rooms. The red alarm display (A) corresponds to DIN 14 623. 7.6.1.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 7.6.3. Connecting the MPA The MPA external detector alarm display is connected using 4 Wago clamps. Clamping on: insert isolated solid wire into the clamp. Disconnecting: Turn wire alternately to the left and right , thus pulling it out of the terminal. Up to 4 detectors can be connected to each MPA. Three inputs (T. 2 – 4) allow adjustment to the various line networks. If used in ex--area, only 2 inputs (T.3 and T.
Product Information MAGIC.SENS -- Product range 8. PI -- 34.65d Order overview 8.1. Detector variants Product ID LE* 4.998.101.151 ST OTC 410 LSN Multi--sensor detector optical / thermal / chemo 4.998.101.152 ST OC 410 LSN Multisensor detector optical / chemo 4.998.130.602 ST OT 400 E LSN Multisensor detector optical / thermal 4.998.121.032 ST O 400 E LSN Optical smoke detector 4.998.130.603 ST T 400 E LSN Thermal detector 4.998.101.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 8.3. Detector base Product ID 4.998.021.535 LE* Designation ST MS 400 Standard -- detector base for surface--mounted and concealed cable insertion 4.998.079.480 ST MSF 400 Detector base with damp room seal, for surface--mounted and concealed cable insertion 4.998.113.025 ST MSC 420 Additional base surface--mounted with damp room seal for surface--mounted cable insertion especially using cable protection ducts.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 8.5. Installation accessories Product ID LE* Designation 4.998.097.924 ST MK 400 Console incl. base, for wall fastening according to DIBt 2.799.271.257 ST Installation angle (without detector base), with mounting material for false floors 8.6. Detector accessories Product ID LE* Designation 4.998.084.709 PAK TP4 400 Support Plate for Detector Zones Identification up to 4m installation height (1 PACK = 50 pieces) 4.998.084.
Product Information MAGIC.SENS -- Product range 9. PI -- 34.65d Installation of the Detector Module . The packaging of the multisensor detector with C--sensor consists of tearproof PE--ALU laminated film and must be cut open carefully. After installation and connection of the base, the detector module is set into the base and turned to the right until it stops. The detector module can only be placed in the base in the correct position! 9.1.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 11. Maintenance and service For maintenance and inspection work on danger detector systems, in Germany the regulations of DIN VDE 0833 apply, which refer to the maintenance interval according to the manufacturer’s instructions. D Maintenance and inspection work should be carried out regularly and by trained personnel. D BOSCH ST recommends a functional and visual inspection at least once a year.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 11.1. Notes for the service: display of the operating data With the exception of the special KKW detector types, for all configured detectors you can use the WinPara programming software (V 4.53 or higher) to display the serial number, degree of contamination, operating hours, and current analog values. Display of the operating data BG--Adr.: module (NVU/LVM) on which the detector or detector line is installed.
Product Information MAGIC.SENS -- Product range PI -- 34.65d Current analog values: -- Optical system value: (display of the current contamination value) 000 . . . 170 Initial set--up value for a new detector. 000 . . . 350 Normal working range. 350 . . . 450 Slight contamination ⇒ exchange detector soon. 450 . . . 510 Heavy contamination ⇒ exchange detector immediately! as of 511 O fault ⇒ optical sensor is switched off! -- Optical system value for special O 400 LSN for RAS 100 LSN: 000 . . .
Product Information MAGIC.SENS -- Product range PI -- 34.65d 11.2. Test Instructions for MAGIC.SENS Fire Detectors The newest generation of MAGIC.SENS OTC 410 LSN/ OC 410 LSN and OC 310 GLT multisensor fire detectors have an additional sensor for CO detection in case of fire. The CO sensor causes improved response behavior and increased malfunction suppression in critical environmental conditions. For fire recognition, MAGIC.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 11.5. Test procedure for MAGIC.SENS OC 310 GLT With the OC 310 you must first test the optical unit with the test aerosol. After triggering the O unit, the detector must be reset. Thus the CO sensor is switched into maintenance mode for 15 minutes and it can then be tested.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 11.7. Coding of the Detector Types With the exception of the O types, all detectors are equipped for identification of the detector type with a colored ring around the central individual display. This simplifies significantly the inspection by service personnel.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 14.1.Service Accessories Product ID LE* Designation 4.998.112.113 ST Universal detector exchanger. 4.998.112.071 ST Test device for optical smoke detectors. 4.998.112.074 ST Solo A3--001 smoke detector testing gas, 250 ml spray can; (1 PACK = 12 pieces) 4.998.142.221 PAK Solo CO testing aerosol for detectors with CO sensors; contents: approx. 4 litres compressed gas; (1 PACK = 12 pieces) 4.998.112.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 15.
Product Information MAGIC.SENS -- Product range PI -- 34.65d 16.
Bosch Security Systems Robert--Koch--Str. 100 D--85521 Ottobrunn Info--Service Telephone: +49 89 6290 -- 1039 Fax: +49 89 6290 -- 1039 www.boschsecurity.com info.service@de.bosch.