User manual
78 en | Appendix NurseCall Main Unit
953.92 | v1.0 | 2007.07 User Manual TeleAlarm SA®
13.5 Paging systems specifications
13.5.1 Multitone RPE670 with ESPA 4.4.4. protocol
Only Alarms/Messages arriving to the Alarm Buffer are transmitted (except "RELAY OFF"). The
transmission is fully alpha-numeric. The Alarms/Messages are repeated every 1 or 3 minutes
until Acknowledgement (see Section 7.4.13 RS232 message setting (toggle), page 55).
The Alarms/Messages are transmitted to the Multitone user number attributed to the
Transmitter (default group = 00).
i
NOTICE!
The system uses 3 protocols, the standard ESPA 4.4.4. protocol, a specific Multitone protocol
(MEP) and the DeTeWe protocol.
i
NOTICE!
Data rate: 9600 Bauds. Transmission: asynchronous with a 10 bit-structure
(1 startbit, 7 databits with even parity, 1 stopbit) in half-duplex mode.
Pagingsystem-ID = 2, NurseCall-ID=1.
Group User number
00 12GG
01 13GG
02 14GG
03 15GG
04 16GG
05 17GG
06 18GG
07 19GG
08 20GG
09 21GG
10 22GG
11 23GG
12 24GG
13 25GG
14 26GG
15 27GG
16 28GG
17 29GG
18 30GG
19 31GG
20 32GG
21 33GG
Table 13.5 Attribution table