User manual

NurseCall Main Unit Programming | en 55
TeleAlarm SA® User Manual 953.92 | v1.0 | 2007.07
7.4.10 Maximum number of Acknowledgement Transmitters (toggle)
This command allows to set the maximum number of Acknowledgement Transmitters
(5=OFF or 32=ON).
The default value is OFF.
1. Type the code 001002.
2. Confirmation message displayed.
7.4.11 Maximum number of Events buffered (toggle)
This command allows to set the number of Events buffered (18=OFF or 50=ON).
The default value is OFF.
1. Type the code 001003.
2. Confirmation message displayed.
7.4.12 Daily message setting (toggle)
Periodically, a message is sent by each Transmitter in order to confirm its good functioning
condition. To avoid to saturate the Event Buffer, disable the daily message check performed by
the NurseCall Main Unit using this command (Parameter = ON).
("Daily message check enabled"=OFF or "Daily message check disabled"=ON).
The default value is OFF.
1. Type the code 001007.
2. Confirmation message displayed.
7.4.13 RS232 message setting (toggle)
This command allows to set the delay for repeating the messages on the RS-232 interface.
("RS-232 repeat message every 3 minutes"=OFF or "RS-232 repeat message every 1
minute"=ON).
The default value is OFF.
1. Type the code 001009.
2. Confirmation message displayed.
!
CAUTION! It is necessary to perform a general RESET before changing this value.
X See Section 7.4.2 Resetting all parameters (including date and time), page 51.