User manual

48 en | Programming NurseCall Main Unit
953.92 | v1.0 | 2007.07 User Manual TeleAlarm SA®
7. If you have selected PAGING, you should
select the protocol (ESPA 4.4.4, DeTeWe or
MEP).
X Use the
and keys for selection.
8. Confirm your selection with .
9. If you have activated the DeTeWe protocol,
you should program the first number (0-9).
X Use the and keys for selection.
10. If you have activated the ESPA 4.4.4 proto-
col, you should program the identification
number (0-9) of the paging system and the
NurseCall system (0-9).
X Use the and keys for field selection
and the and keys for value
changing.
11. Confirm your selection with
.
12. Decide how many characters per information
(criterion, floor, room, bed, position) should
be transmitted to the paging/DECT system
(filter function).
X Use the
and keys for field selection
and the and keys to change the
value. You can choose 0-11 characters for
the criterion, followed by 0-9 spaces.
13. Press
to set the filtering of floor/room/
bed (or single number).
X Use the
and keys for field selection
and the
and keys for values
changing.
14. Press
to set the filtering of the position
(only if Localization Mode is activated).
X Use the
and keys for number of
spaces (0-9) changing.