Technical data

22
Operation
6 720 617 760 (2008/09)
5.4.5 Selecting amplification factor V (parameter: 6C p)
Setting range: 40 % to 100 %
Subject to changes in room temperature, the amplification factor
V influences the heat demand.
B Selecting amplification factor V:
50 %: Select a lower factor to reduce the influence on the
heat demand. The selected room temperature is achieved
after a longer time with only little overshoot.
50 %: Select a higher factor to increase the influence on
the heat demand. The selected room temperature is
achieved quickly with a tendency towards overshooting.
5.4.6 Selecting the maximum flow temperature
(parameter: 6d p)
Setting range: 30 °C to 85 °C
B Select the flow temperature to suit the heating circuit.
5.4.7 Selecting the mixer runtime (parameter: 6E p)
Setting range: 10 s to 600 s
5.4.8 Resetting all adjustments
B Hold down and mode simultaneously for 15 seconds until
the countdown function has expired.
This function returns all controller settings and ad-
justments to their standard settings. Following
such a reset, your installer will need to commission
the controller again.