Technical data

21
Operation
6 720 617 760 (2008/09)
5.4.3 Adjusting the room temperature sensor
(parameter: 6A p)
Setting range: – 3.0 °C (K) to +3.0 °C (K)
Use this parameter if you want to correct the displayed room tem-
perature.
B Position a precision instrument near FR 10. The precision
instrument must not transfer any heat to the FR 10.
B Keep other heat sources, such as sunlight, body heat etc. away
for one hour.
B Adjust the displayed room temperature correction value.
5.4.4 Selecting adjustment factor I (parameter: 6b p)
Setting range: 0 % to 100 %
The adjustment factor I represents the speed with which the con-
stant control deviation of the room temperature is compensated.
B Selecting adjustment factor I:
40 %: Select a lower factor to achieve slight room temper-
ature overshoot through slow correction.
40 %: Select a higher factor to achieve a more rapid cor-
rection by a more severe room temperature overshoot.