Manual

ISP-EMIL-120 LSN Expansion Module | en 23
Bosch Sicherheitssysteme GmbH Installation manual F.01U.076.548 | V3 | 2008.10
Technical Specifications
Operating voltage/current consumption
Operating voltage LSN part 15 to 33 V DC
Other functions 9.0 to 30 V DC
Current consumption LSN part 4.95 mA
Other functions - Max. 370 mA at 12 V
- Max. 180 mA at 28 V
Primary lines PL 1 - PL 6
Connection options 6 detector zones can be programmed as holdup,
intrusion, tamper, lock or entrance
Terminal resistance R
E
= 12.1 kilohm
Interruption voltage Approx. 6 V
Line resistance Max. 100 Ohm
Alarm criteria ± 40% of terminal resistance
Response time < 200 ms
Control outputs S1 - S3
Principle Open collector, active 12 V, 0 V switching
Max. voltage Max. 30 V
Over threshold voltage < 1.4 V
Over threshold current Max. 20 mA
Control output S4
Principle 12 V switching
Over threshold voltage 12.5 V ± 5%
Over threshold current Max. 100 mA
Power supply +12 V for external users
Output voltage +12.5 V DC ± 5%
Output current Max. 100 mA
When connecting an arming device (e.g. NBS 10/coded arming device)
PL 1, 2, 5, 6 and S 1 - S 4 See above
Primary line PL 3 Block-type lock or coded arming device
Primary line PL 4 Coded arming device
Terminal resistors for primary line PL 3 block-type lock R
E
= 12.1 kilohm ±1% (armed)
R
E
= 12.1 kilohm II 3.92 kilohm ±1% (unarmed)
Terminal resistors for primary line PL 3 or PL 4 coded
arming device
R
E
= 12.1 kilohm ±1% (coded arming device invalid)
R
E
= 12.1 kilohm II 3.92 kilohm ±1% (coded arming
device valid)
Environmental conditions/housing
Permissible operating temperature -0 °C to +55 °C
Permissible storage temperature -25 °C to +75 °C
Permissible relative humidity <93%, non-condensing
Protection category IP 30
Environmental class II (VdS 2110)
EMC interference immunity EN 60950, EN 50130, VdS 2110
EMC emitted interference EN 61000-6-3
Housing material and color ABS + PC-FR, signal white (RAL 9003)
Weight Approx. 400 g