Specifications

A-5200-030-260
© 1991-1995 Radionics
74-06176-000-B 9/95
D5200 Programmer Operation Manual
Page 27
6. Sending (Loading) Records
A record can be sent (loaded) into a panel or other device. The D5203 programmer cord can
be connected directly to panels with 4-pin PROG ports and to panels which have phone jack
PROG ports.
Connecting the Programmer
New D5203 Programmer Cord Design
The D5203 programmer cord has been redesigned with a new "Y" cable that eliminates the
need for an adaptor. The new design combines the 4-pin connector plug and the phone jack
connector plug on one cord.
Panel with 4-Pin PROG Port
The D5200 Programmer can be connected directly to a device with a
4-pin male
programming
connector (D4112, D7112, D636, and D2071 control/communicators). An example of this
type of connection is shown in Figure 20.
1. Plug the programmer cord's male phone plug into the D5200 COMMUNICATOR port.
2. Plug the D5203 programmer cord's 4-pin female connector into the 4-pin male
programming (PROG) port on the panel.
Panel with Phone Jack PROG Port
Previously, a D5206 adapter was provided with the D5200 for devices with a
4-pin female
phone jack
(D6112 Control/Communicator, D8112 Control/Communicator, D6500 Receiver).
With the new cord design, the adaptor is no longer necessary An example of this type of
connection is shown in Figure 21.
1. Plug the programmer cord's male phone plug into the D5200 COMMUNICATOR port.
2. Plug the programmer cord's 4-pin male connector into the 4-pin female programming
phone jack (PROG) on the panel.
Sending (Loading) the Program
To load a record into a panel:
1. Scroll to the appropriate product handler from the Product Handlers menu using the red
or keys, and press the red ENTER GROUP key.
2. Scroll to the appropriate record title using the red or keys, and press the red ENTER
GROUP key.
3. When the record title is displayed in the top line, press the red SEND (LOAD) key. The
message SENDING is displayed while the program is downloading into the device. When
the program download is complete, the message SEND SUCCESSFUL is displayed.
Plug In Device: If this message appears, check the connection from the programmer to
the device.
Tweedle: The programmer will tweedle if an attempt is made to load a panel with no
record selected. Before pressing the LOAD key, select a record title and
press the red
ENTER GROUP
key.
INVALID LOCK CODE: Displays if the panel lockcode does not match any of the
lockcodes programmed into the programmer. See the
Lockcodes
chapter for more
information.
SEND FAILURE or Comm Error: These messages are displayed if a communication