Technical data

30 | Fault mode
Gaz 6000 W8 716 473 216 (2014/09)
15.3 Faults that are not shown on the display
15.4 Sensor values
15.4.1 Flow temperature sensor
Appliance faults Remedy
Flow noises Correctly set the pump speed at the pump terminal box.
Heat-up takes too long Correctly set the pump speed at the pump terminal box.
Flue gas readings incorrect; CO levels too high Check gas type.
Check gas supply pressure; adjust if required.
Check flue gas system; clean or repair if required.
Check gas settings; replace gas train if required.
Ignition too violent, poor Check gas type.
Check gas supply pressure; adjust if required.
Check power supply.
Check electrodes with lead; replace if required.
Check flue gas system; clean or repair if required.
Check gas settings; replace gas train if required.
For natural gas: Check external gas flow limiter; replace if required.
Check burner; replace if required.
DHW outlet temperature is
not reached
Check appliance type and gas type; see service function 2.0.A.
Check turbine. Replace if required.
Table 21 Faults that are not shown on the display
Temperature/ °C
Measuring tolerance 10 %
Resistance/
0 33 242
10 19 947
20 12 394
30 7 947
40 5 242
50 3 548
60 2 459
70 1 740
80 1 256
90 923
Table 22