U2 (1) Hot gas temperature too high
On the hot gas temperature sensor
TH4, over 125 °C is measured or
over 110 °C is measured for a period
of 5 minutes. In defrost mode, on
TH5 over 40 °C and on the hot gas
temperature sensor TH4 over
110 °C is measured.
Temperature increase in compressor due to
insufficient refrigerant.
Check inlet overheating.
Check for leaks on the refrigerant lines and seal, if
required, then refill the system.
Faulty ball valve (not completely open). Check if all ball valves are completely open.
Faulty temperature sensor TH4, TH5. Switch the supply voltage off and on again.
Check if fault code “U3” is shown.
If yes, see “Possible solution / check” for “U3”.
Faulty external unit PCB
Faulty linear expansion valve (LEV). Check linear expansion valve (LEV).
U2 (2) Insufficient refrigerant
Faulty if hot gas overheating rises in
cooling mode TH4 to TH5 or in
heating mode TH4-TH6 as follows.
All conditions must be met for
10 minutes (at least for 6 minutes
after compressor start).
Conditions 1:
Compressor is running in heating
mode
Hot gas overheating is 70 °C or
higher
TH6 > TH7 - 5K
TH5 < 35 °C.
Conditions 2:
Compressor is running
Hot gas overheating is 80 °C or
higher in cooling mode
Hot gas overheating is 90 °C or
higher in heating mode
Condensation temperature
TH6 < -40 °C in cooling mode.
Temperature increase in compressor due to
insufficient refrigerant.
Check inlet overheating.
Check for leaks on the refrigerant lines and seal, if
required, then refill the system.
Faulty ball valve (not completely open). Check if all ball valves are completely open.
Faulty temperature sensor TH4, TH5.TH6 Switch the supply voltage off and on again.
Check if fault code “U3” is shown.
If yes, see “Possible solution / check” for “U3”.
Faulty external unit PCB
Faulty linear expansion valve (LEV). Check linear expansion valve (LEV).